Setting:
Description:
Brake Control
Output is set when the motor is in control and the
brake should be released.
The output is set when the motor phase current
check (LX08; initiated by the drive enable and
a direction input) has passed and the motor is
magnetized, the LT01 Brake Release Delay has
expired, and output voltage modulation has begun.
The output turns off after the speed command has
ramped down to zero, the direction input has been
turned off, and the LT10 Brake Drop Delay time
has elapsed or immediately if the drive enable is
dropped at any time or a drive fault occurs.
At Speed
Output is set when there is no speed deviation
between actual and command values, according
to the LX14 Speed Difference.
High Speed *
Output is set whenever the speed is greater than
two times LS01 Leveling Speed.
Deceleration
Output is set when decel is active and the speed
Active *
drops below LX16 Decel Confirmation Speed.
Speed for Door
Output is set when the speed is below LX15 Speed
Pre-opening *
for Pre-Opening to allow pre-opening of the doors.
Leveling Zone *
Output is set when less than 6 inches (15cm) from
the floor. Note: floor position must be on
Main Contact
Output is set when the speed and direction inputs
Control***
are signaled (direction only for analog and serial
speed control modes) Output turns off at end of
run after the current has ramped down and the
drive enters Mode = No Direction (LS). This output
function cannot be used in combination with LI15
Direction Selection Inputs = Down (I6) Input Only.
Refer to LI04 Input Function 1 for further details on
the Main Contact Control.
Motor Overheat
Output is set when terminals T1 & T2 are open.
***
Tells the controller to stop at the next floor
LO - Output Parameters
NUM
4
5
6
7
8
9
10
11