Figure 2-68
regulated DC power through an AC/DC converter. The resulting DC power output is
connected to the PEMs through external cables to supply power to all boards and fan
modules.
Figure 2-68 AC EPS200-4850A power distribution
Table 2-17
Table 2-17 Cables and terminals for the EPS200-4850A
Item
a1,b1,c1,d1
a2,b2,c2,d2
Issue 03 (2017-12-15)
shows the AC power module EPS200-4850A. AC power input is converted into
PDF
a1
A
b1
B
c1
C
d1
D
NOTE
It is recommended that the current specifications of the circuit breakers on the PDF or distribution box
be no less than 16 A
lists the cables and terminals for the AC power module EPS200-4850A.
Power cable
Terminal
Cables
Terminal
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
EPS200-4850A
a2
4850
b2
4850
EMI
c2
4850
d2
4850
Description
Power Cable,300/500V,60227IEC10(BVV),6mm
Jacket(Cores:Blue,Brown),43A,2 Equivalent Cores
Naked Crimping Terminal,OT,6mm
Plating,Insulated Ring Terminal,12~10AWG,yellow
Naked Crimping Terminal,OT,6mm
Plating,Insulated Ring Terminal,12~10AWG,yellow
Monitor and Alarm Cable,
3m,D9M,CC4P0.48B(S),D9M
Wire,450/750V,227 IEC 02(RV)16mm
Wire,450/750V,227 IEC 02(RV)16mm
Naked Crimping Terminal,JG2,16mm
Plated,for OEM
2 Hardware Installation
PEMB
PEMB
PEMB
PEMB
PEMB
2
,M6,Tin
2
,M8,Tin
2
,blue,85A
2
,black,85A
2
,M6,95A,Tin
2
,Black
330