Huawei USG9500 Series Hardware Manual page 335

Hide thumbs Also See for USG9500 Series:
Table of Contents

Advertisement

HUAWEI USG9500 Series
Hardware Guide
Table 2-12
PDF
Table 2-12 Current parameters of circuit breakers and power lines for the PDF (DC PEMB)
Item
Each circuit breaker
(A1,A2,B1,B2,C1,C2,D1,D
2)
Each power supply
(A1,A2,B1,B2,C1,C2,D1,D
2)
If the PDF cannot provide 70 A circuit breakers and full configuration is unnecessary,
select the circuit breaker of each DC line using the following formula
(A1,A2,B1,B2,C1,C2,D1,D2):
I = P / (Vin * D * 4)
I: rated current of the circuit breaker of each line on the PDF, in Ampere (A).
P: total power of each device.
Vin: input voltage of the power supply. (38 < Vin < 72)
D: derating coefficient. The recommended coefficient is 0.8.
4: number of input lines on the power module.
Table 2-13
Table 2-13 PEMB cables
Distance from the PDF to
the Device
Shorter than or equal to 15
m
Issue 03 (2017-12-15)
lists the current parameters of each circuit breaker and each power line for the
Specification
≥ 60 A
≥60 A
describes how to select power cables (a1,a2,b1,b2,c1,c2,d1,d2)
Power Cables a and b
Wire,450/750V,227 IEC
02(RV)16mm
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
Note
To protect power supplies of
different levels, it is
recommended that the
current of the circuit breaker
on the user side should be
greater than or equal to that
of the circuit breaker of the
power module (70 A).
To support the maximum
configuration, it is
recommended that each DC
power line should provide a
minimum of 60 A current.
Each power module should
be equipped with one cable
2
,blue,85A
of this type. The cable
length is determined by an
onsite project survey.
2 Hardware Installation
323