12 Hardware Replacement Methods

12.2.4 Calibration Setting and Confirmation

The touch panel calibration is saved in the control unit. When only the control unit has been replaced, the calibration
must be carried out again.
(Note)
Use a round-tip stick to set the position properly. Take care not to scratch the protective sheet covering
the panel.
(1) Turn the right rotary switch (RSW2), which is on the back of the touch panel display unit, to "F". Then turn the
power ON. After the system starts up, display the calibration setting screen.
(2) On the calibration setting screen, keep pressing the center of the upper-left cross with a red circle for more
than one second. Then lift the stick off the screen.
When the data has been achieved, the upper-left cross turns green and the red circle moves to the bottom-
right.
138