Parameter Setting
This chapter describes the procedure for setting parameters of the IO-Link module.
6.1

CC-Link IE Field Network Parameter Setting

Setting via the engineering tool

Set the parameter of the IO-Link module with the network parameter written to the CPU module of the CC-Link IE Field
Network master station. For details on setting the CC-Link IE Field Network master station, refer to the following.
 User's manual for the master/local module used
Setting procedure
1.
Open the "CC IE Field Configuration" window.
For the master/local module RJ71GF11-T2
[Navigation window]  [Parameter]  [Module Information]  [RJ71GF11-T2]  [Module Parameter]  [Basic Settings]
 [Network Configuration Settings]
2.
Select an IO-Link module from "Module List", and drag and drop it to the list of stations or the network map.
(1)
(2)
(1) List of stations
(2) Network map
3.
Configure the IO-Link module settings.
Item
STA#
Station Type
RX/RY Setting
RWw/RWr Setting
Reserved/Error Invalid Station/System Switching
Monitoring Target Station
*1 Note that necessary points vary depending on the connected IO-Link device.
For details, refer to the manual of the IO-Link device.
Description
Set the station number of a slave station to be connected to the network.
The station number need not be a serial number. (Must not be overlapped.)
Set "Intelligent Device Station".
Set RX and RY assignment. For IO-Link modules, set 80 points or more.
Set RWw and RWr assignment in units of four points. For IO-Link modules, this setting should be
determined by the functions used.
• IO-Link mode: 4 to 132 points (IO-Link module main: 4 points, process data: 0 to 128 points)
• SIO mode: 4 points
Use this to set the slave station as an error invalid station or a switching monitoring target station.