【#24125+15(m-1)】 CNm remote sta pt Remote station points
Select the number of points of the connected remote station.
"m" means the m-th connected station in ascending order of station No. (m= 1 to 64)
The details of setting values differ with each protocol version and station type.
Protocol: Ver.2 (station type: Ver.1, remote I/O station)
0: 0 point (reserved station)
1: 8 points
2: 8 points + 8 points reserved
3: 16 points
4: 32 points
- Setting 0 is valid only for the reserved station. When 0 is set for the other stations, the number of
points will be 32.
- Set the value so that the total number of points of remote I/O stations connected in series will be
multiple of 16.
(Example 1) 2 units of 8 points I/O: Set "1" for each
(Example 2) 3 units of 8 points I/O: Set "1" for the first and the second I/O, "2" for the third.
Protocol: Ver.2 (station type: Ver.1 except remote I/O station)
0: 0 point (reserved station)
1 to 4: Automatically calculated
- 0 point is valid only for the reserved station. When 0 is set for the other stations, the number of
points will be automatically calculated.
- Unless 0 is set, the number of points will be automatically calculated with the number of occupied
stations and the setting value of the extended cycling.
Protocol: Ver.1 (for all station types)
0 to 4: Automatically calculated
- 0 cannot be set even for the reserved station.
- Automatically calculated with the setting value of the number of occupied stations.
---Master station---
Set a value corresponding to the protocol version and the station type.
---Local/standby master station---
Set to "0".
【#24126+15(m-1)】 CNm set rsvd sta Reserved station
Set the reserved/error invalid station.
"m" means the m-th connected station in ascending order of station No. (m= 1 to 64)
0: No setting
1: Reserved station
2: Error invalid station
(Note) Refer to "CC-Link System Master/Local Module User's Manual (SH(NA)-080394E-E)" for the
---Master station---
Set either of "0" to "2".
---Local/standby master station---
Set to "0".
【#24131+15(m-1)】 CNm send size Send buffer size
Set the allocation of the buffer memory size to the local station, standby master station and
intelligent device station when in transient transmission.
"m" means the m-th connected station in ascending order of station No. (m= 1 to 64)
Set "0" when no setting is required.
(Note) The total size of the send/receive buffers must be 4096 (words) or less.
---Master station---
Set a value within the setting range.
---Local/standby master station---
Set to "0".
---Setting range---
0, 64 to 4096 (words)
details of the functions.
M700VS Series Setup Manual
Appendix 1.14 CC-Link Parameters
457