72 Electrical installation

Default I/O connection diagram (ABB standard macro)

Connection
Digital I/O and relay output connections
Analog I/O
Safe torque off (STO)(only on ACS180-04S)
Term.
24 V
21
24V
DGND
22
DGND
DI1
8
DI1
DI2
9
DI2
DI3
10
DI3
11
DI4
DI4
12
DCCOM
DCOM
18
DO
DO
19
DO COM
DO COM
20
DO SRC
DO SRC
NC
5
NC
6
COM
COM
7
NO
NO
AI1/DI5
14
AI1/DI5
AGND
13
AGND
AI2
15
AI2
AGND
16
AGND
AO
17
AO
10V
23
10V
SCREEN
24
SCREEN
S+
1
S+
SGND
2
SGND
S1
3
S1
S2
4
S2
1)
Description
Aux. +24 V DC, max. 100 mA
Aux. voltage output common
Stop (0) / Start (1)
Forward (0) / Reverse (1)
Constant speed selection
Constant speed selection
Digital input common
Running
Digital output common
Digital output auxiliary voltage
Relay output
No fault [Fault (-1)]
Speed reference (0...10V)
Analog input circuit common
Not used
Analog output circuit common
Output frequency (0...20mA)
Ref. voltage +10 V DC
Signal cable shield (screen)
Safe torque off function.
Connected at the factory. Drive starts
only when both circuits are closed.