Auxiliary Output Opening Or Closing In Alarm - Omron E5*C Series User Manual

Digital temperature controllers
Hide thumbs Also See for E5*C Series:
Table of Contents

Advertisement

• Setting Auxiliary Output 2
1
Press the M Key several times in the Advanced Function
Setting Level to display sub2 (Auxiliary Output 2 Assignment).
2
Press the U or D Key to set the parameter to alm2.
The default is alm2 (Alarm 2).
4-6-4

Auxiliary Output Opening or Closing in Alarm

• When "close in alarm" is set, the status of the auxiliary output is output unchanged. When "open in
alarm" is set, the status of the auxiliary output function is reversed before being output.
• Each auxiliary output can be set independently.
• These settings are made in the Auxiliary Output 1 to 4 Open in Alarm parameters (Advanced
Function Setting Level).
• The default is n-o: Close in Alarm.
Close in Alarm
(n-o)
Open in Alarm
(n-c)
• The alarm output will turn OFF (i.e., the relay contacts will open) when power is interrupted and for
about two seconds after the power is turned ON regardless of the setting of the Auxiliary Output 1 to
4 Open in Alarm parameter.
E5@C Digital Temperature Controllers User's Manual (H174)
Auxiliary output
functions 1 to 4
ON
OFF
ON
OFF
Auxiliary output
ON
OFF
OFF
ON
4 Basic Operation
Advanced Function Setting
Level
sub2
Auxiliary Output
2 Assignment
alm2
sub2
alm2
Indicators
(SUB1 to SUB4)
Lit
Not lit
Lit
Not lit
4 - 19