E5Ec-B Terminal Block Wiring Example - Omron E5*C Series User Manual

Digital temperature controllers
Hide thumbs Also See for E5*C Series:
Table of Contents

Advertisement

2-2-5

E5EC-B Terminal Block Wiring Example

 Terminal Arrangement
The terminals block is divided into five types of terminals: control output 1, sensor input, auxiliary outputs, input
power supply, and options.
Input power supply
Control output 1
Auxiliary outputs
Note: The terminals that are shaded gray are not used.
Precautions for Correct Use
When you purchase the Digital Controller, it will be set for a K thermocouple (input type = 5). If a
different sensor is used, an input error (s.err) will occur. Check the setting of the Input Type
parameter.
Control Output 1
 Model Numbers
The specification for control output 1 is given in the following location in the model number.
E5EC-@@ @ @ B M-@@@
Control output 1
Code
RX
QX
CX
 Terminal Details
E
Control output 1
F
E5@C Digital Temperature Controllers User's Manual (H174)
1
33
2
34
3
35
4
36
5
37
38
6
7
39
8
40
9
41
41
10
42
11
43
12
44
13
45
14
46
15
47
16
48
Output type
1 relay output
1 voltage output (for driving SSR)
1 linear current output
RX
Relay output
Control output 1
17
18
Options
19
20
21
22
23
24
25
26
27
28
29
30
31
Sensor input
32
250 VAC, 5 A (resistive load)
12 VDC, 40 mA
4 to 20 mA DC or 0 to 20 mA DC with load of
500 Ω max.
QX
E
+
Voltage output
F
(for driving SSR)
2 Preparations
Specification
CX
E
+
Linear current
Control output 1
F
output
2 - 41