E5CK-T
Specifications for Each Type of Output
Output type
Relay
Voltage (NPN)
Voltage (PNP)
0 to 10 V
4 to 20 mA

Auxiliary Output 1

Terminal numbers 2 and 3 are for auxiliary output 1 (SUB1).
The internal equalizing circuit for auxiliary output 1 is as follows:
5
10
11
12
4
9
3
8
2
7
13
14
1
6
Relay specifications are as follows: SPST-NO, 250 VAC, 1 A
Option
Terminal numbers 1, 13, and 14 are valid only when the option board is set in the Controller.
The following four connections are possible depending on the model of the option board.
5
10
11
12
4
9
3
8
2
7
13
14
1
6
Use event inputs under the following conditions:
Contact input
No-contact input
The polarity for no-contact input is as follows:
+
13
14
1
Transfer output specifications are as follows: 4 to 20 mA, load: 500 Ω max., resolution approx. 2600
Specifications
3 A at 250 VAC
20 mA at 12 VDC (with short-circuit protection)
20 mA at 12 VDC (with short-circuit protection)
0 to 10 VDC, permissible load impedance: 1 kΩ min., resolution: approx. 2,600
4 to 20 mA, permissible load impedance: 500 Ω max., resolution: approx. 2,600
3
2
SD
13
13
RD
14
14
SG
1
1
RS-232C
RS-485
E53-CK01
E53-CK03
ON: 1 kΩ max., OFF: 100 kΩ min.
ON: residual voltage 1.5 V max., OFF: leakage current 0.1 mA max.
+
A
13
13
B
14
14
1
1
Event input
Transfer output
E53-CKB
E53-CKF
E5CK-T
4 to 20mA
179