6 Parameters
prlt
• This parameter sets the key pressing time required to move to the Protect Level from the
Operation Level, the Adjustment Level, or Monitor/Setting Item Level.
Function
Setting
cjc
• This parameter specifies whether cold junction compensation is to be performed
internally by the Digital Controller or to be performed externally when the input type
setting is 5 to 24.
Function
• The cold junction compensation external setting is enabled when the temperature
difference is measured using two thermocouples or two ES1B Sensors.
Setting
 Related Parameters
See
See
Input Type (Initial Setting Level): Page 6-43
6 - 72
Move to Protect Level Time
Setting range
1 to 30
Seconds
Cold Junction Compensation
Method
Setting range
on: Internally, off: Externally
Unit
Default
3
Input type must be thermocouple or infrared
temperature sensor
Default
on
E5@C Digital Temperature Controllers User's Manual (H174)