6 Parameters
lbab
• This parameter sets the LBA band.
• If a control deviation greater than the LBA band is not reduced when the LBA level is
exceeded, an loop burnout is detected.
Function
Temperature input
Setting
Analog input
 Related Parameters
See
See
Process Value/Set Point (Operation Level): Page 6-8
Alarm 1 to 4 Type (Initial Setting Level): Page 6-48
LBA Detection Time (Advanced Function Setting Level): Page 6-79
LBA Level (Advanced Function Setting Level): Page 6-79
6 - 80
LBA Band
Setting range
0.0 to 999.9
0.00 to 99.99
A Standard Model must be used.
Alarm 1 must be assigned.
The alarm type must be set to 12 (LBA).
The LBA detection time must not be 0.
Unit
°C or °F
%FS
E5@C Digital Temperature Controllers User's Manual (H174)
Default
3.0
0.20