E5CC-B
RX (relay)
Code
Output type
RX
Relay
QX
Voltage output (for driving
SSR)
CX
Llinear current output
E5EC/E5AC
RX (relay output)
C
D
QQ (2 voltage outputs (for
driving SSRs))
v
+
+
C
L
D
−
v
+
+
E
L
F
−
Code
Output type
RX
Relay output
QX
Voltage output (for driving SSR)
CX
Linear current output
RR or
2 relay outputs
PR
QQ*
2 voltage outputs
(for driving SSRs)
E5@C Digital Temperature Controllers User's Manual (H174)
QX (voltage output (for
driving SSR))
v
+
A
B
Specification
SPST-NO, 250 VAC, 3 A (resistive load), Electrical
durability: 100,000 operations
PNP, 12 VDC ±20%, 21 mA (with short-circuit protection)
4 to 20 mA DC or 0 to 20 mA DC with load of 500 Ω max.,
Resolution: 10,000
QX (voltage output (for
driving SSR))
v
+
+
C
L
D
−
QR (voltage output (for
driving SSR) and relay
output)
v
+
+
C
L
D
−
E
F
CX (linear current output)
+
A
L
B
-
CX (linear current output)
v
+
+
C
L
D
−
CC (2 linear current
outputs)
v
+
+
C
L
D
−
v
+
+
E
L
F
−
Specification
SPST-NO, 250 VAC, 5 A (resistive load), Electrical life:
100,000 operations
PNP, 12 VDC ±20%, 40 mA (with short-circuit protection)
4 to 20 or 0 to 20 mA DC, Load: 500 Ω max., Resolution:
Approx. 10,000
SPST-NO, 250 VAC, 5 A (resistive load), Electrical life:
100,000 operations
PNP, 12 VDC ±20%, 21 mA (with short-circuit protection)
2 Preparations
v
+
+
A
L
B
-
RR or PR (2 relays)
C
D
E
F
CQ (linear current and
voltage output (for driving
SSR))
v
+
+
C
L
D
−
v
+
+
E
L
F
−
2 - 63
2