Page 1
New Product Digital Temperature Controller E5□C/E5□C-T The E5 C Series Temperature Controller provides a wide lineup of models to meet a variety of applications. These controllers are easy to setup and operate, have unique performance capabilities and offer excellent visibility. Digital Temperature Controllers: E5□C Series 1/32 DIN Models with Screw Terminal Blocks/...
• Easy connections to a PLC with programless communications. E5GC- • Set up the Controller without wiring the power supply by Refer to your OMRON website for the most recent connecting to the computer with a Communications Conversion information on applicable safety standards.
E5GC Model Number Legend and Standard Models Model Number Legend E5GC-@@ @ @ @ M-@@@ (Example: E5GC-RX1A6M-015) −− − − − − −−− B C D E Control No. of Power Model Meaning Terminal Input outputs 1 auxiliary supply Options type type and 2...
Page 4
5.8 mm E54-CT1L* For the system requirements for the CX-Thermo, refer to 12.0 mm E54-CT3 information on the EST2-2C-MV4 on the OMRON website 12.0 mm E54-CT3L* (www.ia.omron.com). *Lead wires are included with these CTs. If UL certification is required, use these CTs.
E5GC Specifications Ratings A in model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85 to 110% of rated supply voltage Power consumption 5.9 VA max. at 100 to 240 VAC, and 3.2 VA max. at 24 VAC or 1.8 W max. at 24 VDC Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II Platinum resistance thermometer: Pt100 or JPt100...
E5GC Alarm Types Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.) Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
Page 8
E5GC *1. With set values 1, 4, and 5, the upper- and lower-limit values can *4. Set value: 5, Upper- and lower-limit with standby sequence be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above at *2 “L”...
Page 9
*5. The unit is determined by the setting of the Integral/Derivative Time Unit parameter. *6. External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time. *7. Refer to your OMRON website for the most recent information on applicable models. *8. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
Programless Controllers: 32 max. (Up to 16 for the FX Series) communica- Applicable PLCs tions OMRON PLCs CS Series, CJ Series, CP Series, NJ Series, or NX1P Mitsubishi Electric PLCs MELSEC Q Series, L Series, FX3 Series, or iQ-R Series...
E5GC External Connections E5GC Control Outputs E5GC-@ @ @ @ @ M - @ @ @ Relay output 250 VAC, 2 A (1) (2)(3)(4)(5) (resistive load) ↑ Terminal type Voltage output (for driving SSR) 12 VDC, 21 mA Auxiliary outputs 1, 2 Linear current output The E5GC is set for a K-type thermocouple (input type = 5) by 0 to 20 mA DC...
Page 12
E5GC Terminal Block Appearance E5GC-@C E5GC-@6 Controllers with Screwless Clamp Terminal Blocks Controllers with Screw Terminal Blocks (M3 Screws) Controllers with Screwless Clamp Terminals Blocks Controllers with Screw Terminal Blocks • Wire stripping length: 8 to 12 mm • Terminal type: Forked or round crimped terminals •...
Page 13
E5GC Dimensions (Unit: mm) Controllers E5GC-@6 Waterproof Packing (Accessory, Y92S-P12 (also available for ordering separately)) Controllers with Screw Mounting Adapter (Accessory, Y92F-53 (also available for ordering separately)) Terminal Blocks Terminal Cover (Accessory, E53-COV27 63.6 (also available for ordering separately)) 44.8 40.8 •...
E5GC Accessories (Order Separately) USB-Serial Conversion Cable (2110) E58-CIFQ2 1510 LED (RD) USB connector (type A plug) Serial connector LED (PWR) LED (SD) Conversion Cable E58-CIFQ2-E Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable (2110) (1510) 1510 E58-CIFQ2 (Order separately) Conversion Cable Note: Always use this product together with the E58-CIFQ2.
Filler 12 dia. (epoxy) E54-CT3 or E54-CT3L Case Maximum continuous heater current: 120 A (50/60 Hz) (PBT) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) 40 × 40 Number of windings: 400±2 Ω Winding resistance: 8±0.8...
E5GC Mounting Adapter Y92F-53 (Two provided.) One pair is provided with the Temperature Controller. Order the Mounting Adapter 34.7 separately if it becomes lost or damaged. 11.8 9.4 Waterproof Packing Y92S-P12 The Waterproof Packing is provided with the Temperature Controller. Order the Waterproof Packing separately if it becomes lost or damaged.
E5CC-U E5CC E5CC-B Use component communications to link Temperature Refer to your OMRON website for the most recent information on Controllers to each other. applicable safety standards. • Set up the Controller without wiring the power supply by Refer to Safety Precautions on 122.
*2. The control output cannot be used as a transfer output. *3. Option 004 can be selected only when "CX" is selected for the control outputs. Note: Draw-out-type models of the E5CC are available. Ask your OMRON representative for details. Heating and Cooling Control...
Page 20
E5CC/E5CC-B/E5CC-U Model Number Legend Models with Push-In Plus Terminal Blocks E5CC-@@ 2 @ B M -@@@ (Example: E5CC-RX2ABM-000) −− − − − − −−− B C D E No. of Power Model Meaning Control outputs Terminal Input auxiliary supply Options 1 and 2 type type...
E5CC/E5CC-B/E5CC-U Model Number Legend Plug-in Models E5CC-@@ @ @ U M -000 (Example: E5CC-RW0AUM-000) B C D E Control No. of Power Model Meaning Terminal Input outputs auxiliary supply Options type type 1 and 2 outputs voltage E5CC 48 × 48 mm Control output 1 Control output 2 Relay output (SPDT)
Page 22
Model For the system requirements for the CX-Thermo, refer to Y92S-P8 information on the EST2-2C-MV4 on the OMRON website Note: The Waterproof Packing is provided only with E5CC/E5CC-B (www.ia.omron.com). Controllers. The E5CC-U cannot be waterproofed even if the Waterproof Packing is attached.
Page 23
E5CC/E5CC-B/E5CC-U Specifications Ratings A in model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85% to 110% of rated supply voltage Models with option selection of 000:5.2 VA max. at 100 to 240 VAC, and 3.1 VA max. at 24 VAC or Power consumption 1.6 W max.
E5CC/E5CC-B/E5CC-U Alarm Types Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
Page 26
E5CC/E5CC-B/E5CC-U *1. With set values 1, 4 and 5, the upper and lower limit values can *4. Set value: 5, Upper- and lower-limit with standby sequence be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above *2 “L”...
Page 27
E5CC/E5CC-B/E5CC-U Characteristics E5CC/E5CC-B (±0.3% of indication value or ±1°C, whichever is greater) ±1 digit max. *1 Thermocouple: Platinum resistance thermometer: (±0.2% of indication value or ±0.8°C, whichever is greater) ±1 digit max. Analog input: ±0.2% FS ±1 digit max. Indication accuracy CT input: ±5% FS ±1 digit max.
Page 28
Voltage Dip/Interrupting Immunity: EN 61000-4-11 *8. The E5CC-U plug-in model is certified for UL listing only when used together with the OMRON P2CF-11 or P2CF-11-E Socket. The P3GA-11 is not certified for UL listing. *9. Access the following website for information on certified models. http://www.ia.omron.com/support/models/index.html *10.Refer to information on maritime standards in Shipping Standards on page 124 for compliance with Lloyd's Standards.
Number of connected Digital Temperature Controllers: 32 max. (Up to 16 for the FX Series) Applicable PLCs E5CC/E5CC-B Programless 250 VAC, 30 VDC OMRON PLCs communications *1 (resistive load) CS Series, CJ Series, CP Series, cosφ = 1 NJ Series, or NX1P...
Page 31
E5CC/E5CC-B/E5CC-U E5CC-B (Push-In Plus Terminal Blocks) E5CC-@@ 2 @ B M - @ @ @ (1) (2) (3) (4) (5) Control output 1 ↑ Terminal type Relay output 250 VAC, 3A Auxiliary outputs 1, 2 The E5CC is set for a K-type thermocouple (resistive load) Voltage output (input type = 5) by default.
Page 32
E5CC/E5CC-B/E5CC-U E5CC-U (Plug-in Models) E5CC- UM-000 The E5CC-U is set for a K-type thermocouple (input type = 5) by default. An input error (s.err) will occur if the input Control output 1 type setting does not agree with the temperature sensor. Auxiliary outputs 1, 2 Check the input type.
Page 33
E5CC/E5CC-B/E5CC-U Nomenclature E5CC Front panel E5CC-B Temperature unit Top View of E5CC Top View of E5CC-B Top View of E5CC-U E5CC-U No. 1 display Operation indicators PV or specified parameter No. 2 display SP or specified parameter value Use the U D Keys to set the parameter.
E5CC/E5CC-B/E5CC-U E5CC-U 76.8 14.2 58.6 48 × 48 44.8 × 44.8 Mounting Adapter (Accessory, Y92F-49 (also available for ordering separately)) The Setup Tool port is on the top of the Temperature Controller. It is used to connect the Temperature Controller to the computer to use the Setup Tool. The E58-CIFQ2 USB-Serial Conversion Cable is required to make the connection.
E5CC/E5CC-B/E5CC-U Waterproof Packing The Waterproof Packing is provided only with the E5CC/E5CC-B. Y92S-P8 (for DIN 48 × 48) It is not included with the E5CC-U. Order the Waterproof Packing separately if it becomes lost or damaged. The Waterproof Packing can be used to achieve an IP66 degree of protection. (Deterioration, shrinking, or hardening of the waterproof packing may occur depending on the operating environment.
Filler 12 dia. (epoxy) E54-CT3 or E54-CT3L Case Maximum continuous heater current: 120 A (50/60 Hz) (PBT) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) 40 × 40 Number of windings: 400±2 Ω Winding resistance: 8±0.8...
Page 37
E5CC/E5CC-B/E5CC-U Adapter Y92F-45 Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@. 2. Only black is available. 3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel.
E5CC/E5CC-B/E5CC-U Watertight Cover Mounting Adapter Y92A-48N Y92F-49 21.9 The Mounting Adapter is provided with the Temperature Controller. Order the Mounting Adapter separately if it becomes lost or damaged. 87.7 79.2 67.6 Protective Cover Protective Cover Y92A-48H Y92A-48D Note: This Protective Cover cannot be used if the Waterproof Packing is installed.
Set up the Controller without wiring the power supply by E5EC-B connecting to the computer with a Communications Conversion Refer to your OMRON website for the most recent information on applicable safety standards. Cable (sold separately). Setup is easy with the CX-Thermo (sold Refer to Safety Precautions on page 122.
*2. The control output cannot be used as a transfer output. *3. A model with four auxiliary outputs must be selected. Note: Draw-out-type models of the E5EC and E5AC are available. Ask your OMRON representative for details. Heating and Cooling Control...
Page 42
E5EC/E5EC-B/E5AC Model Number Legend Models with Push-In Plus Terminal Blocks E5EC-@@ @ @ B M -@@@ (Example: E5EC-RX4ABM-000) −− − − − − −−− B C D E Control No. of Power Model Meaning Terminal outputs auxiliary supply Input type Options type 1 and 2 outputs...
CX-Thermo version 4.67 or higher is required for the E5CC-B Temperature Controller. linear current output type. Waterproof Packing For the system requirements for the CX-Thermo, refer to information on the EST2-2C-MV4 on the OMRON website Applicable Controller Model (www.ia.omron.com). E5EC/E5EC-B...
Page 44
E5EC/E5EC-B/E5AC Specifications Ratings A in model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85 to 110% of rated supply voltage Models with option selection of 000: 6.6 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or E5EC/ 2.3 W max.
E5EC/E5EC-B/E5AC Alarm Types Each alarm can be independently set to one of the following 19 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
Page 47
E5EC/E5EC-B/E5AC *1. With set values 1, 4 and 5, the upper and lower limit values can *4. Set value: 5, Upper- and lower-limit with standby sequence be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above *2 “L”...
Page 48
*5. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time. *6. Refer to your OMRON website for the most recent information on applicable models. *7. Refer to information on maritime standards in Shipping Standards on page 124 for compliance with Lloyd's Standards.
PLCs. No communications programming is required. Number of connected Digital Temperature Controllers: 32 max. (Up to 16 for the FX Series) Applicable PLCs Programless OMRON PLCs communications *1 CS Series, CJ Series, CP Series, NJ Series, or NX1P Mitsubishi Electric PLCs...
Page 50
E5EC/E5EC-B/E5AC External Connections E5EC/E5AC (Screw Terminal Blocks) E5EC-@@ 4 @ 5 M - @ @ @ E5AC-@@ 4 @ 5 M - @ @ @ (1) (2) (3) (4) (5) (1) (2) (3) (4) (5) The E5EC is set for a K-type thermocouple (input type = 5) by default.
Page 51
E5EC/E5EC-B/E5AC E5EC-B (Push-In Plus Terminal Blocks) E5EC-@@ @ @ B M - @ @ @ (6) Options (2) (3) (4) (5) Communications, 2 event inputs Communications, 2 event inputs, and 1 CT input ↑ B(+) B(+) Terminal type RS-485 RS-485 Control output 1 Auxiliary outputs 1, 2, 3, 4 The E5EC is set for a K-type...
Page 52
E5EC/E5EC-B/E5AC Isolation/Insulation Block Diagrams Models with 2 Auxiliary Outputs Models with 4 Auxiliary Outputs Sensor input, CT inputs, potentiometer input, and remote SP input Sensor input, CT inputs, and remote SP input Communications and event inputs Communications and event inputs Voltage output (for driving SSR), Voltage output (for driving SSR) and transfer output Power...
Page 53
E5EC/E5EC-B/E5AC Dimensions (Unit: mm) Controllers E5EC (64) Waterproof Packing (Accessory, Y92S-P9 Mounting Adapter (also available for (Accessory, Y92F-51 ordering separately)) (also available for E5EC-B ordering separately)) (71.4) 67.4 Mounting Adapter Waterproof Packing (Accessory, Y92S-P9 (Accessory, Y92F-51 (also available for (also available for ordering separately)) ordering separately)) •...
Page 54
E5EC/E5EC-B/E5AC E5AC (64) 96 x 96 91 x 91 Waterproof Packing Mounting Adapter (Accessory, Y92S-P10 (Accessory, Y92F-51 (also available for (also available for ordering separately)) ordering separately)) • Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller.
Page 55
E5EC/E5EC-B/E5AC Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ2 (2110) 1510 LED (RD) USB connector (type A plug) Serial connector LED (PWR) LED (SD) Conversion Cable E58-CIFQ2-E Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable (2110) (1510) 1510 E58-CIFQ2 (Order Separately) Conversion Cable Note: Always use this product together with the E58-CIFQ2.
Filler 12 dia. (epoxy) E54-CT3 or E54-CT3L Case Maximum continuous heater current: 120 A (50/60 Hz) (PBT) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) 40 × 40 Number of windings: 400±2 Ω Winding resistance: 8±0.8...
Page 58
• Easy connections to a PLC with programless communications. E5DC-B • Set up the Controller without wiring the power supply by connecting to Refer to your OMRON website for the most recent the computer with a Communications Conversion Cable (sold separately). information on applicable safety standards.
E5DC/E5DC-B Model Number Legend and Standard Models Model Number Legend Models with Screw Terminal Blocks E5DC-@@ @ @ @ M -@@@ (Example: E5DC-RX0ASM-015) −− − − − − −−− B C D E Control No. of Power Model Meaning Terminal Input outputs 1 auxiliary...
Page 60
E5DC/E5DC-B Model Number Legend Models with Push-In Plus Terminal Blocks E5DC-@@ @ @ B M-@@@ (Example: E5DC-QX2ABM-002) −− − − − − −−− B C D E Control No. of Power Model Meaning Terminal Input outputs 1 auxiliary supply Options type type and 2...
Page 61
EST2-2C-MV4 Note: CX-Thermo version 4.6 or higher is required for the E5DC. CX-Thermo version 4.69 or higher is required for the E5DC-B. For the system requirements for the CX-Thermo, refer to information on the EST2-2C-MV4 on the OMRON website (www.ia.omron.com).
Page 62
E5DC/E5DC-B Specifications Ratings A in model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85 to 110% of rated supply voltage Power consumption 4.9 VA max. at 100 to 240 VAC, and 2.8 VA max. at 24 VDC or 1.5 W max. at 24 VDC Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II Platinum resistance thermometer: Pt100 or JPt100...
E5DC/E5DC-B Alarm Types Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (See note.) Auxiliary outputs are allocated to alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
Page 65
E5DC/E5DC-B *1. With set values 1, 4, and 5, the upper- and lower-limit values can *4. Set value: 5, Upper- and lower-limit with standby sequence be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above at *2 “L”...
Page 66
*6. External serial communications (RS-485) and USB-Serial Conversion Cable communications can be used at the same time. *7. Refer to your OMRON website for the most recent information on applicable models. *8. Refer to information on maritime standards in Shipping Standards on page 124 for compliance with Lloyd's Standards.
E5DC/E5DC-B External Connections E5DC (Models with Screw Terminal Blocks) Control output Auxiliary outputs 1, 2 The E5DC is set for a K-type thermocouple (input type = 5) by default. Relay outputs Relay output An input error (s.err) will occur if the input type setting does not agree 250 VAC: 2 A (resistive load) 250 VAC, 3 A (resistive load) with the temperature sensor.
Page 69
E5DC/E5DC-B E5DC-B (Models with Push-In Plus Terminal Blocks) Control output Auxiliary outputs 1, 2 The E5DC-B is set for a K-type thermocouple (input type = 5) by default. Relay outputs An input error (s.err) will occur if the input type setting does not agree Relay output 250 VAC: 2 A (resistive load) with the temperature sensor.
Page 70
E5DC/E5DC-B Nomenclature E5DC Front panel E5DC-B Bottom View of E5DC/E5DC-B No. 1 display PV or specified parameter Operation indicators No.2 display SP or specified parameter value Press O Key once to go to Use the M Key to change to another Adjustment Level.
Page 71
E5DC/E5DC-B Dimensions (Unit: mm) Controllers E5DC (85) 22.5 22.5 +1.15 -0.2 +1.15 -0.2 The above figure shows the Mounting Adapter Terminal Unit (E5DC-SCT1S) Terminal Unit attached to (Y92F-53)(Order separately) the Main Unit. E5DC-B (90) (6.5) 22.5 (6.5) 22.5 +1.15 -0.2 +1.15 -0.2 The above figure shows the...
E5DC/E5DC-B Accessories (Order Separately) Terminal Unit Push-In Plus Terminal Unit E5DC-SCT1S E5DC-SCT1B (6.5) 22.5 30.7 22.5 36.2 +1.15 +1.15 -0.2 -0.2 USB-Serial Conversion Cable E58-CIFQ2 (2110) 1510 LED (RD) USB connector (type A plug) Serial connector LED (PWR) LED (SD) Conversion Cable E58-CIFQ2-E Conversion Cable...
E5DC/E5DC-B Current Transformers E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Filler E54-CT1 or E54-CT1L 5.8 dia. (epoxy) Maximum continuous heater current: 50 A (50/60 Hz) Case ± Number of windings: ± Ω Winding resistance: 10.5 100V Frequency: 50 Hz ∞...
Filler 12 dia. (epoxy) E54-CT3 or E54-CT3L Case Maximum continuous heater current: 120 A (50/60 Hz) (PBT) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) 40 × 40 Number of windings: 400±2 Ω Winding resistance: 8±0.8...
E5DC/E5DC-B Short Bars Mounting Adapters Y92S-P11 (Four included.) Y92F-53 (Two included.) Use this product to connect between terminals (for power supplies, This accessory is not included with the communications, etc.) when you use multiple E5DC Controllers. product. Order it separately to mount the product to a panel.
E5DC/E5DC-B Connector Cover E53-COV26 Male connector cover Female connector cover E5DC-B Push-In Plus Terminal Units are mounted with both a male and female connector cover (E53-COV26). Order the connector cover separately if it becomes lost or damaged.
Page 78
48 48 mm E5CC-T • Set up the Controller without wiring the power supply by connecting to Refer to your OMRON website for the most recent the computer with a Communications Conversion Cable (sold information on applicable safety standards.
E5CC-T Model Number Legend and Standard Models Model Number Legend Models with Screw Terminal Blocks E5CC-T @@3 @5 M -@@@ (Example: E5CC-TRX3A5M-000) −−−−−− −−− A BC D E No. of Power Model Meaning Control outputs Terminal Input auxiliary supply Options 1 and 2 type type...
Page 80
Note: CX-Thermo version 4.61 or higher is required for the E5CC-T. Temperature Controller. The E53-COV10 cannot be used. For the system requirements for the CX-Thermo, refer to Refer to page 89 for the mounted dimensions. information on the EST2-2C-MV4 on the OMRON website (www.ia.omron.com). Waterproof Packing Model...
Page 81
E5CC-T Specifications Ratings A in model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85 to 110% of rated supply voltage Power consumption 7.5 VA max. at 100 to 240 VAC, and 4.1 VA max. at 24 VAC or 2.3 W max. at 24 VDC Temperature input Thermocouple: K, J, T, E, L, U, N, R, S, B, C/W, or PL II Platinum resistance thermometer: Pt100 or JPt100...
E5CC-T Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor Platinum resistance Infrared temperature Thermocouple type thermometer sensor Sensor 10 to 60 to 115 to 140 to Pt100 JPt100 C/W PLII 70°C 120°C 165°C 260°C specification 2300 2300 1800 1800 1700 1700 1700 1600...
Page 83
E5CC-T Alarm Types Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
Page 84
E5CC-T *1. With set values 1, 4 and 5, the upper and lower limit values can *4. Set value: 5, Upper- and lower-limit with standby sequence be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above *2 “L”...
Page 85
*4. The unit is determined by the setting of the Integral/Derivative Time Unit parameter. *5. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time. *6. Refer to your OMRON website for the most recent information on applicable models. *7. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
E5CC-T Program Control Number of programs (patterns) Number of segments (steps) Time setting (Segment set with set point and time.) Segment setting method Slope setting (Segment set with segment type, set point, slope, and time.) 0 h 0 min to 99 h 59 min Segment times 0 min 0 s to 99 min 59 s Alarm setting...
Programless Number of connected Digital Temperature communica- Controllers: 32 max. tions * Applicable PLCs OMRON PLCs CS Series, CJ Series, CP E5CC-T Series, NJ Series, or NX1P 250 VAC, 30 VDC Mitsubishi Electric PLCs MELSEC Q Series, L Series, (resistive load) or iQ-R Series cosφ...
E5CC-T External Connections E5CC-T Control output 1 Relay output E5CC 250 VAC, 3 A (2) (3) (4) (5) (resistive load) Voltage output Terminal type (for driving SSR) Auxiliary outputs 12 VDC, 21 mA The E5CC-T is set for a K-type thermocouple (input Control output 2 Linear current output Relay output...
Page 89
E5CC-T Nomenclature E5CC-T Front panel Temperature unit Operation indicators No. 1 display PV or specified monitor/setting parameter Top View of E5CC-T No. 2 display Press O Key once to go to SP or specified monitor/parameter value Program Setting Level. Top-panel Setup Tool port Press O Key for at least 3 seconds to go to Initial Setting Use the...
Page 90
E5CC-T Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ2 (2110) 1510 LED (RD) USB connector (type A plug) Serial connector LED (PWR) LED (SD) Terminal Covers E53-COV17 E53-COV23 (Three Covers provided.) 48.8 Terminal Cover (E53-COV23) 44.8 Waterproof Packing Y92S-P8 (for DIN 48 × 48) The Waterproof Packing is provided with the Temperature Controller.
E5CC-T Current Transformers E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Filler E54-CT1 or E54-CT1L 5.8 dia. (epoxy) Maximum continuous heater current: 50 A (50/60 Hz) Case ± Number of windings: ± Ω Winding resistance: 10.5 100V Frequency: 50 Hz ∞...
Filler 12 dia. (epoxy) E54-CT3 or E54-CT3L Case Maximum continuous heater current: 120 A (50/60 Hz) (PBT) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) 40 × 40 Number of windings: 400±2 Ω Winding resistance: 8±0.8...
Page 93
E5CC-T Adapter Y92F-45 Note: 1. Use this Adapter when the Front Panel has already been prepared for the E5B@. 2. Only black is available. 3. You cannot use the E58-CIFQ2 USB-Serial Conversion Cable if you use the Y92F-45 Adapter. To use the USB-Serial Conversion Cable to make the settings, do so before you mount the Temperature Controller in the panel.
Page 94
E5CC-T Watertight Cover Mounting Adapter Y92A-48N Y92F-49 21.9 The Mounting Adapter is provided with the Temperature Controller. Order the Mounting Adapter separately if it becomes lost or damaged. 87.7 79.2 67.6 28.9 Protective Cover Protective Cover Y92A-48H Y92A-48D Note: This Protective Cover cannot be used if the Waterproof Packing is installed.
Page 96
E5EC-T • Models are available with up to 4 auxiliary outputs, up to 6 event Refer to your OMRON website for the most recent inputs, and a transfer output to cover a wide range of applications. information on applicable safety standards.
Page 97
E5EC-T/E5AC-T Model Number Legend and Standard Models Model Number Legend Models with Screw Terminal Blocks E5EC-T@@ 4 @ 5 M -@@@ (Example: E5EC-TRX4A5M-000) −−− − − − −−− A B C D E E5AC-T@@ 4 @ 5 M -@@@ (Example: E5AC-TRX4A5M-000) −−−−...
Page 98
Note: CX-Thermo version 4.61 or higher is required for the E5EC-T/ E53-COV24 (3pcs) E5AC-T. For the system requirements for the CX-Thermo, refer to Note: The Terminal Covers E53-COV24 are provided with the Digital information on the EST2-2C-MV4 on the OMRON website Temperature Controller. (www.ia.omron.com). Waterproof Packing Applicable Controller...
Page 99
E5EC-T/E5AC-T Specifications Ratings A in model number: 100 to 240 VAC, 50/60 Hz Power supply voltage D in model number: 24 VAC, 50/60 Hz; 24 VDC Operating voltage range 85 to 110% of rated supply voltage E5EC-T 8.7 VA max. at 100 to 240 VAC, and 5.5 VA max. at 24 VAC or 3.2 W max. at 24 VDC Power consumption E5AC-T 9.0 VA max.
Page 100
E5EC-T/E5AC-T Input Ranges Thermocouple/Platinum Resistance Thermometer (Universal inputs) Sensor Platinum resistance Infrared temperature Thermocouple type thermometer sensor Sensor 10 to 60 to 115 to 140 to Pt100 JPt100 C/W PLII 70°C 120°C 165°C 260°C specification 2300 2300 1800 1800 1700 1700 1700 1600...
Page 101
E5EC-T/E5AC-T Alarm Types Each alarm can be independently set to one of the following 17 alarm types. The default is 2: Upper limit. (see note.) Auxiliary outputs are allocated for alarms. ON delays and OFF delays (0 to 999 s) can also be specified. Note: In the default settings for models with HB or HS alarms, alarm 1 is set to a heater alarm (HA) and the Alarm Type 1 parameter is not displayed.
Page 102
E5EC-T/E5AC-T *1. With set values 1, 4 and 5, the upper and lower limit values can *4. Set value: 5, Upper- and lower-limit with standby sequence be set independently for each alarm type, and are expressed as For Upper- and Lower-Limit Alarm Described Above *2 “L”...
Page 103
*4. The unit is determined by the setting of the Integral/Derivative Time Unit parameter. *5. External communications (RS-485) and USB-serial conversion cable communications can be used at the same time. *6. Refer to your OMRON website for the most recent information on applicable models. *7. Industrial electromagnetic environment (EN/IEC 61326-1 Table 2)
Page 104
E5EC-T/E5AC-T Program Control Number of programs (patterns) Number of segments (steps) Time setting (Segment set with set point and time.) Segment setting method Slope setting (Segment set with segment type, set point, slope, and time.) 0 h 0 min to 99 h 59 min Segment times 0 min 0 s to 99 min 59 s Alarm setting...
Page 105
Programless Number of connected Digital Temperature Controllers: communica- 32 max. tions * Applicable PLCs OMRON PLCs CS Series, CJ Series, CP Series, NJ Series, or NX1P Mitsubishi Electric PLCs MELSEC Q Series, L Series, or iQ-R Series Switching current (A)
Page 106
E5EC-T/E5AC-T External Connections E5EC-T/E5AC-T E5EC E5AC (2) (3) (4) (5) (2) (3) (4) (5) Terminal type Terminal type Control output 1 Control output 2 Auxiliary outputs Relay output Relay output Relay output Models with 4 auxiliary 250 VAC, 5 A 250 VAC, 5A (resistive load) Use no-voltage inputs for the event inputs.
Page 107
E5EC-T/E5AC-T Nomenclature E5EC-T Front panel Top View of E5EC-T No. 1 display Temperature unit PV or specified monitor/parameter Operation indicators No. 2 display Top-panel SP or specified monitor/parameter value Setup Tool port No. 3 display Use S Key to change the Program No., segment No., digit (default setting).
Page 108
E5EC-T/E5AC-T Dimensions (Unit: mm) Controllers E5EC-T • Setup Tool ports are provided as (64) standard feature. Use these ports to connect a computer to the Digital Temperature Controller. The E58- CIFQ2 USB-Serial Conversion Cable is required to connect to the port on the top panel.
Page 109
E5EC-T/E5AC-T E5AC-T (64) 96 x 96 91 x 91 Waterproof Packing Mounting Adapter (Accessory, Y92S-P10 (Accessory, Y92F-51 (also available for (also available for ordering separately)) ordering separately)) • Setup Tool ports are provided as standard feature. Use these ports to connect a computer to the Digital Temperature Controller.
Page 110
E5EC-T/E5AC-T Accessories (Order Separately) USB-Serial Conversion Cable E58-CIFQ2 (2110) 1510 LED (RD) USB connector (type A plug) Serial connector LED (PWR) LED (SD) Conversion Cable E58-CIFQ2-E Conversion Cable Connecting to the E58-CIFQ2 USB-Serial Conversion Cable (2110) (1510) 1510 E58-CIFQ2 (Order Separately) Conversion Cable Note: Always use this product together with the E58-CIFQ2.
Page 111
E5EC-T/E5AC-T Watertight Cover Watertight Cover Y92A-96N (96 × 96) Y92A-49N (48 × 96) 21.9 21.9 131.7 131.7 115.6 28.9 67.6 28.9 Current Transformers E54-CT1 Thru-current (Io) vs. Output Voltage (Eo) (Reference Values) Filler E54-CT1 or E54-CT1L 5.8 dia. (epoxy) Maximum continuous heater current: 50 A (50/60 Hz) Case ±...
Page 112
Filler 12 dia. (epoxy) E54-CT3 or E54-CT3L Case Maximum continuous heater current: 120 A (50/60 Hz) (PBT) (Maximum continuous heater current for an OMRON Digital Temperature Controller is 50 A.) 40 × 40 Number of windings: 400±2 Ω Winding resistance: 8±0.8...
E5@C/E5@C-T Operation Setting Levels Diagram E5C This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Control stops when you move from the operation level to the initial setting level.
Page 115
E5@C/E5@C-T E5C-T This diagram shows all of the setting levels. To move to the advanced function setting level and calibration level, you must enter passwords. Some parameters are not displayed depending on the protect level setting and the conditions of use. Press O and M Keys Protect Level for at least 1 s.
Page 116
E5@C/E5@C-T Operation Parameters E5@C The following pages describe the parameters set in each level. Pressing the M (Mode) Key at the last parameter in each level returns to the top parameter in that level. Some parameters may not be displayed depending on the model and other settings. Press the S Key*2 Power ON Starting in Manual Mode.
Page 117
E5@C/E5@C-T Monitor/Setting Item Level Monitor/Setting Monitor/Setting Monitor/Setting Monitor/Setting Monitor/Setting Item Display 4 Item Display 1 Item Display 3 Item Display 5 Item Display 2 Note: The monitor/setting items to be displayed is set in the Monitor/Setting Item 1 to 5 parameters (advanced function setting level). Press the O Key for at least 1 s.
Page 118
E5@C/E5@C-T E5@C-T Some parameters may not be displayed depending on the model and other settings. Starting in manual mode Monitor/Setting Item Level PF Monitor/ Power ON PF Monitor/Setting Manual Control Level Setting Item Item display 2 to 5 display 1 * The monitor/setting items to display are set in the Monitor/Setting Item 1 to 5 parameters PV/Manual MV (Advanced Function Setting Level).
Page 119
E5@C/E5@C-T Press O Key Protect Level for at least 1 s. Press O + M Key for at least 3 s. Operation/Adjustment oapt pfpt PF Key Protect pmov Protect Move to Protect Level Initial Setting/ Parameter Mask Enable icpt pmsk Press O + M Key for at least 3 s.
Page 120
E5@C/E5@C-T Advanced Function Setting Level Direct Setting of Position init mant pmvd Manual Output Method Proportional MV Parameter Initialization hold PV Rate of Change mani pvrp pend Manual MV Initial Value Program End ON Time Calculation Period Heating/Cooling Tuning hctm Standby Time Unit Method ompw...
Page 121
E5@C/E5@C-T Error Displays (Troubleshooting) When an error occurs, the No. 1 display or No. 2 display shows the error code. Take necessary measure according to the error code, referring the following table. Display Name Meaning Action Operation The input value exceeded the control Check the wiring for input to be sure After the error occurs and it is range.*...
E5@C/E5@C-T Safety Precautions Be sure to read the precautions for all E5@C/E5@C-T models in the website at: http://www.ia.omron.com/. Warning Indications Minor electric shock or fire may occasionally occur. Indicates a potentially hazardous Do not use any cables that are damaged.
Page 123
E5@C/E5@C-T Precautions for Safe Use Be sure to observe the following precautions to prevent malfunction 6. Do not wire the terminals that are not used. 7. Use a commercial power supply for the power supply voltage input or adverse affects on the performance or functionality of the product. to a Digital Temperature Controller with AC input specifications.
E5@C/E5@C-T 23.Do not disconnect the Communications Conversion Cable or the Shipping Standards USB-Serial Conversion Cable while communications are in progress. Damage or malfunction may occur. The E5CC, E5CC-B, E5CC-U, E5EC, E5EC-B, E5AC, and E5DC 24.Do not touch the external power supply terminals or other metal comply with Lloyd's standards.
E5@C/E5@C-T Measurement Accuracy 5. Wiring When linking the units together, connect the power cable only to 1. When extending or connecting the thermocouple lead wire, be sure to the unit at the left end of the linkage block. Incorrect wiring can be use compensating wires that match the thermocouple types.
Page 126
E5@C/E5@C-T E5CC/E5CC-B/E5CC-U/E5CC-T E5DC/E5DC-B • E5CC/E5CC-T Adapter Panel There are two models of Terminal Covers that you can use with the E5CC/E5CC-T. Terminal Cover Terminal Cover (E53-COV17) (E53-COV23) (Sold separately) Adapter Terminal Unit Main Unit Water Proof Packing Panel • E5CC-U 1.
E5@C/E5@C-T Removing the Main Unit Removing the Main Unit Press in the two hooks on the Main Unit and remove the Main Unit from the Terminal Unit. (2) Pull out the Main Unit. (1) Push in the hooks. End Plate Installation Make sure to attach PFP-M End Plates to the ends of the Units.
Page 128
E5@C/E5@C-T Removing from the DIN Track 5. Insert the main unit into the mounting hole in the panel, and then mount the terminal unit. 1. Remove the Main Unit from the Terminal Unit. 2. Remove the Terminal Units. 6. Push the adapter from the terminal unit side until it comes into contact with the panel to temporarily secure the unit, and then tighten the two fastening screws on the adapter.
Page 129
E5@C/E5@C-T Attaching the Connector Cover 2. Remove the Main Unit from the Terminal Unit. E5DC-B For male connector covers 1. Press on the connector cover until it clicks into place. There is no vertical direction for male connector covers. For female connector covers 3.
E5@C/E5@C-T Mounting the Terminal Cover Attaching the End Cover E5CC/E5CC-T E5DC/E5DC-B Slightly bend the E53-COV23 Terminal Cover to attach it to the 1. Install the E5DC/E5DC-B in a panel. terminal block as shown in the following diagram. The Terminal Cover cannot be attached in the opposite direction.
E5@C/E5@C-T Removing the Digital Temperature Controller from the case Removing the draw-out jig when only one hook is caught E5GC in the draw-out jig insertion hole You can use the Y92F-55 Draw-out Jig to remove the interior body of 1. Pull the Draw-out Jig slowly in the direction shown in the figure. (This step is the same even if the other hook is caught.) the Digital Temperature Controller from the case to perform 2.
E5@C/E5@C-T Crimp Terminal E5GC (Controllers with Screwless Clamp For the E5CC/E5EC/E5AC/E5DC/E5GC (Controllers with Screw Terminal Blocks) Terminal Blocks) or E5@C-T, use the following types of crimp 1. Connection Method for Screwless Clamp Terminals terminals for M3 screws. The same method is used to connect stranded wires, solid wires, and ferrules.
Page 133
E5@C/E5@C-T 3. Recommended Wire Size and Ferrules E5@C-B (Controllers with Push-In Plus Terminal Wire Size Blocks) Use the wire sizes and stripping lengths given in the following table. 1. Connecting Wires to the Push-In Plus Terminal Block Part Names of the Terminal Block Wire Size Stripping length AWG24 to AWG18...
∗ Side view of the product SDIS 0.4✕2.5✕75 Weidmuller 10 to 15° 9900 (-2.5✕75) Vessel * OMRON's exclusive purchase model XW4Z-00B is available to 30° order as SZF 0-0,4 x 2,5 (manufactured by Phoenix Contact). Flat-blade screwdriver ∗ Side view of the product 3.
Unit, the positive and negative thermocouple input terminals of the Unit are short-circuited, and the ambient temperature is stable. Should the Unit malfunction during the guarantee period, OMRON shall repair the Unit or replace any parts of the Unit at the expense of OMRON.
Page 137
OMRON AUTOMATION AMERICAS HEADQUARTERS • Chicago, IL USA • 847.843.7900 • 800.556.6766 • automation.omron.com OMRON CANADA, INC. • HEAD OFFICE OMRON ELETRÔNICA DO BRASIL LTDA • HEAD OFFICE Toronto, ON, Canada • 416.286.6465 • 866.986.6766 • automation.omron.com São Paulo, SP, Brasil • 55.11.2101.6300 • www.omron.com.br OMRON ELECTRONICS DE MEXICO •...