2 Preparations
 Linked Mounting on DIN Track
1
Remove the connector cover
of the Terminal Unit from the
side that is to be linked, and
mount the Unit on the DIN
Track.
2
Link the connectors of the
Terminal Units.
3
Wire the Terminal Units.
4
Insert the Main Unit into the
Terminal Unit.
Precautions for Correct Use
• When N units are linked together, the inrush current will be equal to N times that for 1 unit. Be
sure to use the external fuse with the appropriate fusing characteristics, and the breaker with
the appropriate tripping characteristics to ensure that the fuse does not melt and the breaker is
not activated due to the inrush current. The inrush current per Unit is 30 A or less.
• Do not remove the connector cover from connectors that are not to be linked. The connector
covers have been mounted on the product during shipment.
• Do not add or separate the units during power-on.
2 - 16
End Plate
2
1
3
4
E5@C Digital Temperature Controllers User's Manual (H174)
Connector cover
(Provided)
Left side: