Setting Object (Class Id: 371 Hex) - Omron K6CM User Manual

Motor condition, monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

8 Monitoring and Setting Using the EtherNet/IP Devices
8-3-4

Setting Object (Class ID: 371 hex)

This object sets up the K6CM device itself and sets up measurement and alarm.
Service Code
Service code
02 hex
10 hex
01 hex
0E hex
*1. Be sure to set "0" to the attribute IDs: 64 hex and 65 hex.
When you perform various resets, set with Set_Attribute_Single.
*2. Attribute IDs 64 to 6D hex and 6E to 78 hex are read.
Functions implemented by upgrading such as A0 hex of attribute ID can not be read by Get_Attributes_All,
but can be read by Get_Attribute_Single.
The data size is 42 bytes for Get_Attributes_All.
Class ID
Specify 371 hex.
Instance ID
Specify 01 hex.
Attribute ID
Common to K6CM
Attri-
Parameter
bute ID
name
64 hex
Software reset Restarts the K6CM device. It is used to
65 hex
Max./min.
reset
66 hex
Display value
type
8 - 18
Service name
Set_Attributes_All
Write values to all attributes.
Set_Attribute_Single
Write the value of the speci-
fied attribute.
Get_Attributes_All
Reads the values of all attri-
butes.
Get _Attribute_Single
Reads the value of the speci-
fied attribute.
Description
validate the setting after changing the set-
*1
ting value.
Rising from 0 to 1: Execute (soft reset)
Initializes the MAX / MIN value.
OFF to ON: Execute (initialize max. and
min. value)
Sets which measurement value is dis-
played in the 7 segment display on the
front of the K6CM.
0: PV
1: MIN
2: MAX
Description
Not supported.
*1
Not supported.
Not supported.
Not supported.
Attri-
bute
Write
Write
Write
K6CM Motor Condition Monitoring Device User's Manual (N219)
Supported services
Classes
Instances
Supported.
Supported.
*2
Supported.
Supported.
Data
Data type
Default value
UINT
0000 hex
UINT
0000 hex
UINT
0000 hex

Advertisement

Table of Contents
loading

Table of Contents