Monitoring Using The Tag Data Link; Connection Setting - Omron K6CM User Manual

Motor condition, monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

8-2

Monitoring Using the Tag Data Link

8-2-1

Connection setting

Originator device (PLC) Input tag set
Target device
(K6CM device)
Packet interval (RPI)
Timeout value
Create tag set of PLC side with size of 44 bytes.
*1.
Precautions for Correct Use
If I/O memory addresses are specified for the communications areas, the information in the
communications areas will be cleared when the operating mode of the PLC changes unless
addresses in the Area, which are maintained, are specified.
K6CM Motor Condition Monitoring Device User's Manual (N219)
8 Monitoring and Setting Using the EtherNet/IP Devices
Setting items
Connection type
Output tag set
Setting contents
Specify the tag set on the PLC side of 44 bytes.
Specify "Point to Point connection".
Instance ID: 100, size is fixed to 44 bytes.
250 ms to 10000 ms (default: 250 ms)
Multiples of RPI (4 times, 8 times, 16 times, ..., 512 times)
*1
8
8 - 5