Omron K6CM User Manual page 222

Motor condition, monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

Appendices
Item
Measuring
Individual alarm
and monitor-
by measurement
ing method
value
Comprehensive
alarm as K6CM
device
Output
Output form
Functions
Output rating
EtherNet/IP
Connected device
Communications
type
*1. Judgment of comprehensive alarm as a device:
Comprehensive alarm threshold setting (Warning) setting: A state in which "Critical" does not exist in the mea-
surement value and "Warning" exists even in even one.
• Threshold (Critical) setting for comprehensive alarm: A state in which at least one of the measurement val-
ues has "Critical".
*2. Each transistor output 1 and 2 can not be set differently.
*3. A self-diagnosis error occurs due to any one of the following reasons: Refer to Trouble shooting on page 9-1
when confirming self-diagnosis error.
Measurement CPU error
Measurement CPU data flash error
Main CPU error
Main CPU data flash error
Input unit error
Ratings
Item
Power supply voltage
Allowable operating voltage range
Power supply frequency range
Power consumption
Startup time at power ON
A - 6
Compare the measured value with the alarm set value (Critical level and Warning level)
and output an alarm (Critical, Warning).
When multiple alarms (Critical, Warning) occur, they are output by OR logic*1with priority
of Critical> Warning.
Transistor output (normally closed)
The following 3 outputs
• Transistor output 1: Comprehensive alarm (Warning) output (Output type*2 can be set
to Normally open or Normally closed)
• Transistor output 2: Comprehensive alarm (Critical) output (Output type * 2 can be set
to Normally open or Normally closed)
• Transistor output 3: Self diagnostic error output*3 (Normally closed fixed. Self-diagno-
sis error occurrence: OFF, self-diagnosis error not occurred: ON)
Contact configuration: NPN open collector
Rated voltage: 24 VDC
Maximum current: 50 mA
Software tool, or EtherNet/IP compatible equipment such as PC, PLC
• CIP message communication: reception of CIP command
• Tag data link: Output only
K6CM-
MA: 100 to 240 VAC, 50/60 Hz (Alternating current)
K6CM-
MD: 24 VAC, 50/60 Hz, 24 VDC (Both direct and alternating current)
85% to 110% of the rated power supply voltage
45 to 65 Hz
K6CM-VBM
24 VAC/24 VDC: 3.8 VA/2.1W max.
100 to 240 VAC: 7.1 VA max.
K6CM-ISM
24 VAC/24 VDC: 3.7 VA/2.0W max.
100 to 240 VAC: 6.2 VA max.
K6CM-CIM
24 VAC/24 VDC: 3.1 VA/1.6W max.
100 to 240 VAC: 6.0 VA max.
10 s or less
Note : This is the time from power-ON until the measuring and monitoring start or "-
- - -" is displayed.
After that, the measurement value is displayed after the sampling time has
elapsed.
K6CM Motor Condition Monitoring Device User's Manual (N219)
Specifications
Specifications