Omron K6CM User Manual page 191

Motor condition, monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

Attri-
Parameter name
bute ID
6F hex
Using inverter
70 hex
Inverter special mea-
surement
71 hex
Insulation resistance
alarm (Warning)
72 hex
Insulation resistance
alarm (Critical)
73 hex
Reserved
74 hex
Reserved
75 hex
Reserved
76 hex
Reserved
77 hex
Reserved
78 hex
Reserved
K6CM Motor Condition Monitoring Device User's Manual (N219)
8 Monitoring and Setting Using the EtherNet/IP Devices
Description
Sets the presence or absence of
the inverter.
0: OFF (No inverter)
1: ON (with inverter)
(For 3 phase 4 wires N phase
ground load side delta connec-
tion, use with no inverter.If you
have an inverter you can not do
the correct measurement.)
Sets the Inverter Special measure-
ment.
0: OFF
1: ON
Special calculation to do when
inverter frequency and commercial
frequency are close.
Note : With or without inverter =
"with inverter" only valid
For how to use this function, refer
to the Wiring Diagram of the Insu-
lation Resistance Type (K6CM-IS)
on page 5-21 in 5-5 I/O wiring on
page 5-20.
Sets the insulation resistance
alarm threshold (Warning).
0 to 9999 (unit: 0.001 MΩ)
(0000 to 270F hex)
Sets the insulation resistance
alarm threshold (Critical)).
0 to 9999 (unit: 0.001 MΩ)
(0000 to 270F hex)
Reserved
Reserved
Reserved
Reserved
Reserved
Reserved
Data
Attri-
bute
Data type
Default value
Write
UINT
0000 hex
Write
UINT
0000 hex
Write
UINT
0320 hex (800)
(Unit: 0.001
MΩ)
Write
UINT
400
(Unit: 0.001
MΩ)
Write
UINT
0000 hex
Write
UINT
0000 hex
Write
UINT
0000 hex
Write
UINT
0000 hex
Write
UINT
0000 hex
Write
UINT
0000 hex
8
8 - 21