8 Monitoring and Setting Using the EtherNet/IP Devices
*1. K6CM status
The K6CM status is handled as 2-byte data consisting of bit data in the table.
Example: TR1 to TR3 are "ON" and the measurement state is "During measurement and monitoring".
The 15th, 14th, 13th and 9th bits are all "1", so it is "1110 0010 0000 0000" in binary notation and "200" in
hexadecimal notation. In the log file (CSV) of the Motor condition monitoring Tool, the K6CM status is in hexa-
decimal notation.
Bit position
00
01
02
03
04
05
06
07
08
09
10
11
12
13
14
15
Precautions for Correct Use
If the trigger function is used, when reading the measurement value with the tag data link, be
sure to read it when the "Monitoring condition" bit (bit 09) of the K6CM status is 1 (ON).
If reading is performed when the "Measurement state" bit is 0 (OFF), there is a possibility that
the value before measurement and monitoring (i.e., 0) or the value held after measurement and
monitoring is being read.
8 - 10
Status
Measurement CPU error
Measurement CPU data flash error
Main CPU error
Main CPU data flash error
Reserved.
Reserved.
Reserved.
Reserved.
Running Time status
Monitoring condition
Reserved.
Reserved.
Trigger input
TR 1 (transistor 1output state)
TR 2 (transistor 2output state)
TR 3 (transistor 3output state)
Not occurred
Not occurred
Not occurred
Not occurred
Unreached
Measuring and moni-
toring is stopped
OFF
OFF
OFF
OFF
K6CM Motor Condition Monitoring Device User's Manual (N219)
Bit contents
0
1
Occurrence
Occurrence
Occurrence
Occurrence
Reached
Measuring and moni-
toring
ON
ON
ON
ON