Omron K6CM User Manual page 192

Motor condition, monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

8 Monitoring and Setting Using the EtherNet/IP Devices
Comprehensive current diagnosis type (K6CM-CIM)
Attri-
Parameter
bute ID
name
6E hex
Current range
6F hex
Reserved.
70 hex
Reserved.
71 hex
Current alarm
(Warning)
72 hex
Current alarm
(Critical)
73 hex
Degradation
level alarm
(Warning)
74 hex
Degradation
level alarm
(Critical)
75 hex
Reserved
76 hex
Reserved
77 hex
Reserved
78 hex
Reserved
8 - 22
Description
Sets the current range.
0: 5 A
1: 25 A
2: 100 A
3: 200 A
4: 400 A
5: 600 A
Reserved.
Reserved.
Sets the current alarm (Warning).
0 to 9999
(Unit in the 5 A range: 0.01 A)
(Unit in other ranges: 0.1 A)
(0000 to 270F hex)
Sets the current alarm (Critical).
0 to 9999
(Unit in the 5 A range: 0.01 A)
(Unit in other ranges: 0.1 A)
(0000 to 270F hex)
Sets the degradation level alarm (Warn-
ing).
0 to 999
(0000 to 03E7 hex)
Sets the degradation level alarm (Critical).
0 to 999
(0000 to 03E7 hex)
Reserved
Reserved
Reserved
Reserved
K6CM Motor Condition Monitoring Device User's Manual (N219)
Data
Attri-
bute
Data type
Default value
Write
UINT
0003 hex
Write
UINT
0000 hex
Write
UINT
0000 hex
Write
UINT
07D0 hex
(2000)
(Unit in the 5 A
range: 0.01 A)
(Unit in other
ranges: 0.1 A)
Write
UINT
07D0 hex
(2000)
(Unit in the 5 A
range: 0.01 A)
(Unit in other
ranges: 0.1 A)
Write
UINT
001E hex (30)
Write
UINT
0032 hex (50)
Write
UINT
0000 hex
Write
UINT
0000 hex
Write
UINT
0000 hex
Write
UINT
0000 hex