The Push-In Plus Terminal Block; How To Use The Push-In Plus Terminal Block - Omron K6CM User Manual

Motor condition, monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

5-3-1

the Push-In Plus Terminal Block

Item
Construction
Applicable wires
Applicable wire size
Wire insertion force
Screwdriver insertion force
Wire stripping length
Ferrule length
Recommended flat-blade
screwdriver
Current capacity
Number of insertions
Recommended ferrules
5-3-2

How to use the Push-In Plus Terminal Block

Nomenclature of the Terminal Block
<Upper side>
Connecting Wires with Ferrules and Solid Wires
Insert the solid wire or ferrule straight into the terminal block until the end strikes the terminal block.
<Upper side>
If a wire is difficult to connect because it is too thin, use a flat-blade screwdriver in the same way as
when connecting stranded wire.
K6CM Motor Condition Monitoring Device User's Manual (N219)
Push-in compatible with 1-pole 2-terminal interwiring wiring
Hands free
Front-in front and front-release
Stranded wires, solid wires, or ferrules
2
0.25 to 1.5 mm
(AWG24 to AWG16)
8 N max. for AWG20 wire
15 N max.
10 mm, 12 mm
8 mm, 10 mm
XW4Z-00B (Omron) (Refer to the "Recommended Flat-blade Screwdriver" in 5-3-3 Recom-
mended Ferrules and Crimp Tools on page 5-17.)
10 A (per pole)
50 times
Refer to the 5-3-3 Recommended Ferrules and Crimp Tools on page 5-17.
Terminal
(Insertion) hole
Release hole
Terminal
(Insertion) hole
Ferrules
Release hole
5 Installation and Wiring
Specification
<Lower side>
Release hole
Terminal
(Insertion) hole
<Lower side>
Release hole
Ferrules
Terminal
(Insertion) hole
5