Omron K6CM User Manual page 154

Motor condition, monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

6 How to Use the Software Tool
Setting parameter name
Insulation resistance alarm
threshold (Critical)
Transistor output type
Comprehensive current diagnosis Type K6CM-CI
Setting parameter name
Display value type
Trigger mode
Trigger type
* Setting is not required when
the trigger mode is "Always ".
Trigger level
* Setting is not required when
the trigger mode is "Always"
or " External trigger".
Monitoring time
* Setting is not required when
the trigger mode is "Always"
or the trigger type is "Level ".
Alarm latch
Use Running Time
Moving Average times
Current range
Current alarm threshold
(Warning)
Current alarm threshold (Crit-
ical)
Degradation level alarm
threshold (Warning)
Degradation level alarm
threshold (Critical)
Transistor output type
6 - 24
Setting range
0.000 to 9.999
0: Normally closed,
1: Normally open
Setting range
0: PV, 1: MIN, 2: MAX
0: Always, 1: External trigger,
2: Internal trigger
0: Rising, 1: Falling edge, 2:
Level
0.00 to 99.99
0.1 to 600.0
0: Disable, 1: Enable
0: OFF, 1: ON
0: OFF, 1: 2 times, 2: 4 times,
3: 8 times, 4: 16 times, 5: 32
times
0: 5 A, 1: 25 A, 2: 100 A, 3:
200 A, 4: 400 A, 5: 600 A
Current range 5 A: 0.00 to
99.99
Other current range: 0.0 to
999.9
Current range 5 A: 0.00 to
99.99
Other current range: 0.0 to
999.9
0 to 999
0 to 999
0: Normally closed,
1: Normally open
K6CM Motor Condition Monitoring Device User's Manual (N219)
Description
Set a threshold value for out-
putting individual alarm (Criti-
cal) of the insulation
resistance.
Select transistor output type.
Description
Set which measured value is
displayed in the K6CM
device.
Set the measurement mode.
For external trigger or internal
trigger, set the starting condi-
tion of the trigger measure-
ment.
For internal trigger, set the
measurement value to start
trigger measurement.
Set the time to continue the
measurement when the trig-
ger mode is set to "External
trigger" or "Internal trigger"
with the trigger type "Rising"
or "Falling edge ".
Set the latch function when
an alarm is detected
Set the function to detect the
life of the K6CM device?
The averaging process is per-
formed on the past n times of
measured values.
Note n is the moving average
number on the shown left col-
umn.
Set the range according to
the current flowing in the
equipment to be monitored
Set a threshold value for out-
putting individual alarm
(Warning) of the current.
Set a threshold value for out-
putting individual alarm (Criti-
cal) of the current.
Set a threshold value for out-
putting individual alarm
(Warning) of the degradation
level.
Set a threshold value for out-
putting individual alarm (Criti-
cal) of the degradation level.
Select transistor output type.
Default
0.400
0
Default
0: PV
0: Always
0: Rising
0.00
0.1
1: Enable
0: OFF
0: OFF
3: 200 A
Current range 5 A: 20.00
Other current range: 200.0
Current range 5 A: 20.00
Other current range: 200.0
30
50
0