Main Unit Setting Object (Class ID: 377 hex)

This object writes the setting parameters (such as the existence of alarm latch, transistor output
method, enabling or disabling of "Use predicted arrival time", etc.) of the Main Unit.
Alternatively, it performs each operation instruction (such as K6PM-TH sensor registration, K6PM-TH
sensor location registration, reset of the maximum temperature of all sensors connected to the corre-
sponding Main Unit, etc.).
Note Software reset uses the Identity object (Class ID: 01 hex).
Service Codes
Service
Service name
code
01 hex
Get_Attributes_All
02 hex
Set_Attributes_All
0E hex
Get_Attribute_Single Reads the value of the specified attribute.
10 hex
Set_Attribute_Single Write the value of the specified attribute.
4B hex
Sensor_Registration
4C hex
Sensor_-
Mode_Change
*1. Reset occurs after the command ends normally.
If the mode is already a transition target, an error response (0B hex) is returned.
If 0 sensors are registered for K6PM-TH sensor type registration, an error response (0C hex) is returned.
*2. The K6PM-TH sensor number in the position adjustment mode is reflected in the "Target sensor in position
adjustment mode" of the Main Unit monitor object.
At the same time, bits 5 and 6 of the Main Unit status are updated.
An error response (10 hex) is returned when in the monitoring mode.
K6PM-TH Thermal Condition Monitoring Device User's Manual (H231)
5 Monitoring and Setting with the EtherNet/IP Communications
Description
Reads the values of all attributes.
Write values to all attributes.
K6PM-TH sensor registration
*1
Request data
...
1: Cancel sensor registration. (Change to sen-
sor search mode),
2: Register sensor. (Change to monitoring
mode)
(0001 to 0002 hex, Data type: UINT)
Change the K6PM-TH sensor mode
*2
Request data
...
0: K6PM-TH sensor search mode,
1: K6PM-TH sensor 1 position adjustment
mode,
2: K6PM-TH sensor 2 position adjustment
mode,
31: K6PM-TH sensor 31 position adjustment
mode (0000 to 001F hex, Data type: UINT)
Not supported
Not supported
Not supported
Not supported
Not supported
Not supported
:
Supported services
Classes
Instances
Supported
Supported
Supported
Supported
Supported
Supported
5 - 17