5 Installation and Wiring
Connecting Stranded Wires
Use the following procedure to connect the wires to the terminal block.
1
Hold a flat-blade screwdriver at an angle and insert it into the release hole.
The angle should be between 10° and 15°.
If the flat-blade screwdriver is inserted correctly, you will feel the spring in the release hole.
The terminal block may be damaged if you insert a flat-blade screwdriver in the release
hole with excessive force. Insert the flat-blade screwdriver into the release holes with a
force of 15 N or less.
2
With the flat-blade screwdriver still inserted into the release hole, insert the wire into the terminal
hole until it strikes the terminal block.
3
Remove the flat-blade screwdriver from the release hole.
Checking Connection
• After the insertion, pull gently on the wire to make sure that it will not come off and the wire is
securely fastened to the terminal block.
• If you use a ferrule with a conductor length of 10 mm, part of the conductor may be visible after the
ferrule is inserted into the terminal block, but the product insulation distance will still be satisfied.
• To prevent short circuits, insert the stripped part of a stranded or solid wire or the conductor part of a
ferrule until it is hidden inside the terminal insertion hole.
• For the stranded wires, make sure that some of the wires from adjacent terminals are not accidentally
inserted.
(Refer to the following diagram.)
Removing Wires from the Push-In Plus Terminal Block
5 - 16
CAUTION
<Upper side>
(2)
Wire
(3)
(1)
Flat-blade screwdriver
10 to 15°
Flat-blade screwdriver
<Lower side>
Flat-blade screwdriver
(3)
Flat-blade screwdriver
10 to 15°
K6CM Motor Condition Monitoring Device User's Manual (N219)
(1)
Wire
(2)