Omron K6CM User Manual page 99

Motor condition, monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

9
In the "Set the connecting means for the target device.", set the following.
Check one of the following check boxes.
• Acquired from BOOTP server
• Fixed setting with IP address acquired from BOOTP server
• Fixed setting
When "Fixed setting" is checked, set the IP address, subnet mask, default gateway.
Note When "Fixed setting with IP address obtained from BOOTP server" or "Acquired from BOOTP
server" is checked, set the IP address to be acquired from the BOOTP server here.
If the device obtains a value different from that value from the BOOTP server, the Motor condition
monitoring Tool will not be able to access that device. In that case, delete the relevant device with
the [Delete device] Button of the tool buttons, and then re-register the device with the IP address
obtained from the BOOTP server by the [Add device] Button.
Precautions for Correct Use
When setting the IP address of the K6CM to "Fixed setting", set the IP address of the computer
to the IP address of the same segment as the K6CM.For details of the setting method, refer
to4-3-1 IP Address Setting of Your PC on page 4-25.
10
Click the [Next] Button.
The following [Parameter setting] wizard screen will be displayed. (Set the parameters as nec-
essary.) For details, refer to "6-2-1 Settings for Each Monitor Type of K6CM devices on page
6-22".
Be sure to set the parameters in the table below before starting measurement.
Comprehensive cur-
rent diagnosis type
Vibration & tempera-
ture type
K6CM Motor Condition Monitoring Device User's Manual (N219)
Model
Parameter name
Current range
Temperature unit
4 Introduction of the Software Tool
Setting value
Input the set value according to CT to be used.
0: Rated CT 5 A is connected (K6CM-CICB005)
1: Rated CT 25 A is connected (K6CM-CICB025)
2: Rated CT 100 A is connected (K6CM-CICB100)
3: Rated CT200 A is connected (K6CM-CICB200)
4: Rated CT 400 A is connected (K6CM-CICB400)
5: Rated CT 600 A is connected (K6CM-CICB600)
Select the temperature unit of motor temperature and
Temperature gap.
0: °C
1: °F
4
4 - 33