3 Measuring and Monitoring Mechanism
3-3

Monitoring Mechanism

3-3-1

Types of Individual Alarms

K6CM's individual alarm type and threshold setting range are as follows.
For individual alarms, it is possible to set the level of Warning and Critical, respectively.
Monitor types
Vibration & tempera-
ture type
Insulation resistance
type
Comprehensive cur-
rent diagnosis type
*1. In the case of the upper limit alarm, it is necessary that the threshold of Critical > Warning is satisfied. If Critical
threshold ≤ Warning threshold, the Warning threshold is ignored and only the Critical threshold exists.
In the case of the lower limit alarm, it is necessary that the threshold of Critical <Warning is set. If Critical thresh-
old ≥ Warning threshold, the Warning threshold is ignored and only the Critical threshold exists.
3-3-2

Comprehensive Alarm Judgment

Comprehensive alarms are judged as integrated OR logic with the priority order as "Critical" > "Warn-
ing" > "Normal" for each individual alarm.
It is as follows.
Types of comprehensive alarm
Normal
Warning
Critical
Example: When the measurement value is two:
Individual alarm
Normal and Normal
Warning and Normal
Warning and Warning
Critical and Normal
Critical and Warning
Critical and Critical
Note To specify the type of individual alarm that exceeds the alarm threshold, operate the DISP key in the front of
the K6CM device to check the measured values by monitoring type.
3 - 12
Models
Individual alarm type
K6CM-VBM
Acceleration alarm
Velocity alarm
Motor temperature alarm
Temperature gap alarm
K6CM-ISM
Insulation resistance
alarm
K6CM-CIM
Degradation level alarm
Current alarm
When there is neither "Critical" nor "Warning" in the individual alarm.
When there is not even one "Critical" level in the individual alarm, and at least one "Warn-
ing" level.
When there is at least one "Critical" level in the individual alarm.
Comprehensive alarm
Normal
Warning
Warning
Critical
Critical
Critical
Upper or
Threshold setting
lower
range
*1
limit
Upper
0.00 to 99.99 G
Upper
0.00 to 99.99 ms
Upper
0 to 9999 deg
Upper
0 to 9999 deg
Lower
0.000 to 9.999 MΩ
Upper
0 to 999
Upper
Rating 5 A: 00.00 to
99.99 A
Rating 25 A / 100 A /
200 A / 400 A / 600 A:
0.0 to 999.9 A
Status
K6CM Motor Condition Monitoring Device User's Manual (N219)
*1
Level
Warning
Critical
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes