Name
Front
[ARM RST]
Release the alarm latch (cancellation by
operat-
Key
communication is impossible).
ing part
Note : Setting the alarm latch to "L" will latch
[DISP] Key
Switch the unit of measurement value (moni-
toring category)
Press the
When pressed at the same time for 5 seconds
[ALM RST]
or more, initialize all settings of the K6CM
and [DISP]
device and restore the Factory default.
Keys simulta-
neously
Transis-
Transistor
Warning output of comprehensive alarm.(*2)
tor Out-
Output 1
Transistor output type can be set to Normally
put
Closed or Normally Open. (* 3)
Transistor
Critical output of comprehensive alarm.(*2)
Output 2
Transistor output type can be set to Normally
Closed or Normally Open. (* 3)
Transistor
Self-diagnosis error output.
Output 3
Transistor output type can be set to Normally
Closed only.
* Self-diagnosis error is a function to detect
errors of the K6CM device itself.
EtherNet/IP port
Port for connecting Ethernet cable for com-
munications with the software tool, PLC, and
PC.
*1. "MON" always lights up when there is no trigger. When there is a trigger, it lights up during measuring and monitoring. It
turns off after measuring and monitoring is not started yet, and after measuring and monitoring is completed (only when
using the trigger function).
*2. The output state (ON/OFF) of the transistor is held at the end of measuring and monitoring (only when using the trigger
function).
*3. The setting function of transistor output type can be used with EIP CPU version 1.10 or later. It is fixed to Normally
closed with EIP CPU version less than 1.10.
K6CM Motor Condition Monitoring Device User's Manual (N219)
the alarm condition of comprehensive
alarm (Warning or Critical) (alarm bar,
transistor outputs 1 and 2). Release
this latched state.
2 Nomenclature and Functions
Meaning
If you press the [ALM RST] key during measuring and moni-
toring, it returns to the comprehensive alarm state at that point
(both the alarm bar and transistor outputs 1 and 2).
Every time it is pressed, the unit of measurement value
changes as follows.
• Vibration & temperature type: "G" → "mm/s" → "T" → "∆T"
(→ "G")
• Insulation resistance type: "MΩ" → "mA" (→ "MΩ")
• Comprehensive current diagnosis type: "Cim" → "A" (→
"Cim")
----
• Normally closed output type
ON: Comprehensive alarm is normal
OFF: Comprehensive alarm is warning or critical
• Normally open output type
ON: Comprehensive alarm is warning or critical
OFF: Comprehensive alarm is normal
It turns OFF regardless of the output type in either of the fol-
lowing cases.
• Measurement and monitoring is not started (only when
using the trigger function).
• Self-diagnosis error
• Normally closed output type
ON: Comprehensive alarm is normal
OFF: Comprehensive alarm is warning or critical
• Normally open output type
ON: Comprehensive alarm is warning or critical
OFF: Comprehensive alarm is normal
It turns OFF regardless of the output type in either of the fol-
lowing cases.
• Measurement and monitoring is not started (only when
using the trigger function).
• Self-diagnosis error
In the following cases, ON
• When Self-diagnosis error does not occur
In the following cases, OFF
• Self-diagnosis error occurrence
It is with straight / cross cable automatic discrimination func-
tion.
2
2 - 5