Omron K6CM User Manual page 189

Motor condition, monitoring device
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

Attri-
Parameter
bute ID
name
67 hex
Trigger mode
68 hex
Trigger type
69 hex
Trigger level
6A hex
Monitoring
time
6B hex
Alarm latch
6C hex
Use Running
Time
6D hex
Moving aver-
age times
A0 hex
Transistor out-
put type
*1. If you execute the software reset after writing to the attribute ID 65 to 78 hex or A 0 hex, wait for about 1 sec-
ond, considering the time until these setting values are saved, and then execute the software reset.
*2. Transistor output type is a function implemented by version upgrade.
EIP CPU version: Implemented in the K6C device with version 1.10 or higher. The EIP CPU version can be
confirmed by the following method.
• Confirm the description of the side label of the K6C device
• Confirmation the read data using the software tool or EtherNet/IP communication
Vibration & temperature type (K6CM-VBM)
Attri-
Parameter
bute ID
name
6E hex
Temperature
unit
K6CM Motor Condition Monitoring Device User's Manual (N219)
8 Monitoring and Setting Using the EtherNet/IP Devices
Description
Selects the trigger mode.
0: Always
1: External trigger
2: Internal trigger
Sets the trigger type.
0: Rising
1: Falling edge
2: Level
Sets the trigger level.
Note : Unit and decimal point position
follow measured values. (Refer to
Section 6 How to Use the Soft-
ware Tool)
Sets the monitoring time.
1 to 6000 (unit: 0.1 sec)
Sets enable/disable of alarm latch func-
tion.
0: Disable (no latch)
1: Enable (with latch)
Sets the usage or nonuse of K6CM
remaining capacity function.
0: OFF (not used)
1: ON (use)
Every time the measured value is sam-
pled, the data of the past n times including
the sampling data of that time is averaged.
0: OFF
1: 2 times
2: 4 times
3: 8 times
4: 16 times
5: 32 times
Select transistor output type.
*2
0: Normally closed
1: Normally open
Description
Sets the temperature unit.
0: °C
1: °F
Data
Attri-
bute
Data type
Default value
Write
UINT
0000 hex
Write
UINT
0000 hex
Write
UINT
0000 hex
Write
UINT
0001 hex (1)
(Unit: 0.1 sec-
onds)
Write
UINT
0001 hex
Write
UINT
0000 hex
Write
UINT
Vibration &
temperature
type, Insulation
resistance type:
0000 hex
Comprehen-
sive current
diagnosis type:
0003 hex
Write
UINT
0000 hex
Data
Attri-
bute
Data type
Default value
Write
UINT
0000 hex
8
8 - 19

Advertisement

Table of Contents
loading