FC 300 Design Guide

Initialization to Default Settings

"
Initialize the adjustable frequency drive to default settings in two ways:
Recommended initialization (via par. 14-22)
1.
Select par. 14-22
Press [OK]
2.
Select "Initialisation"
3.
Press [OK]
4.
Cut off the mains supply and wait until
5.
the display turns off.
Reconnect the mains supply - the adjustable
6.
frequency drive is now reset.
Manual initialization
1.
Disconnect from mains and wait until
the display turns off.
Press [Status] - [Main Menu] - [OK]
2.
at the same time:
Reconnect mains supply while pressing the keys.
3.
4.
Release the keys after 5 s.
5.
The adjustable frequency drive is now
programmed according to default settings.
NOTE
When you carry out manual initialization,
you also reset serial communication,
RFI filter settings (par. 14-50)
and fault log settings.
How to Program
MG.33.B6.22 - VLT is a registered Danfoss trademark
Par. 14-22 initializes everything except:
14-50
RFI 1
8-30
Protocol
8-31
Address
8-32
Baud Rate
8-35
Minimum Response Delay
8-36
Max Response Delay
8-37
Max Inter-char Delay
15-00 to 15-05
Operating data
15-20 to 15-22
Historic log
15-30 to 15-32
Fault log
This parameter initializes everything except:
15-00
Operating Hours
15-03
Power-ups
15-04
Over temps
15-05
Over volts
149