Contents FC 300 Programming Guide Contents 1 Introduction 1.1.1 Approvals 1.1.2 Symbols 1.1.3 Abbreviations 1.1.4 Definitions 1.1.5 Electrical Wiring - Control Cables 2 How to Programme 2.1 The Graphical and Numerical Local Control Panels 2.1.1 How to Programme on the Graphical LCP 2.1.2 The LCD-Display...
Page 2
Contents FC 300 Programming Guide 3.18 Parameters: 17-** Motor Feedb. Option 3.19 Parameters: 18-** Data Readouts 2 3.20 Parameters: 30-** Special Features 3.21 Parameters: 35-** Sensor Input Option 4 Parameter Lists 5 Troubleshooting 5.1.1 Warnings/Alarm Messages Index ® MG.33.M9.02 - VLT...
Automatic Motor Adaptation Software version: 6.1x Current limit °C Degrees Celsius This Programming Guide can be used for all FC 300 frequency Direct current converters with software version 6.1x. Drive Dependent D-TYPE The software version number can be seen from par. 15-43 Software Electro Magnetic Compatibility Version.
Introduction FC 300 Programming Guide 1.1.4 Definitions Instantaneous motor voltage. Frequency converter: VLT,MAX Maximum output current. Rated motor voltage (nameplate data). VLT,N Break-away torque Rated output current supplied by the frequency converter. VLT, MAX Maximum output voltage. Input: Control command Start and stop the connected motor by means of LCP and digital inputs.
Page 5
Introduction FC 300 Programming Guide metres from the frequency converter, i.e. in a front panel by means of the installation kit option. Determines the relationship between the reference input at 0% value (typically 0V, 0mA, 4mA) and the resulting reference.
Page 6
Introduction FC 300 Programming Guide Trip A state entered in fault situations, e.g. if the frequency converter is subject to an over-temperature or when the The voltage of the frequency converter is dangerous frequency converter is protecting the motor, process or whenever connected to mains.
Page 7
Hoists and cranes: IEC 60204-32 instructions in the Safe Stop section of the VLT Lifts: EN 81 AutomationDrive FC 300 Design Guide. Protection Mode Control signals from, or internally within, the Once a hardware limit on motor current or dc-link voltage is frequency converter may in rare cases be activated exceeded the frequency converter will enter “Protection...
Introduction FC 300 Programming Guide 1.1.5 Electrical Wiring - Control Cables Illustration 1.1: Diagram showing all electrical terminals without options. Terminal 37 is the input to be used for Safe Stop. For instructions on Safe Stop installation please refer to the section Safe Stop Installation of the Design Guide.
Page 9
Introduction FC 300 Programming Guide Input polarity of control terminals 1.1.6 Start/Stop Terminal 18 = par. 5-10 Terminal 18 Digital Input [8] Start Terminal 27 = par. 5-12 Terminal 27 Digital Input [0] No operation (Default coast inverse) Terminal 37 = Safe stop (where available!) NOTE Control cables must be screened/armoured.
Page 11
Introduction FC 300 Programming Guide 1.1.9 Potentiometer Reference Voltage reference via a potentiometer: Reference Source 1 = [1] Analog input 53 (default) Terminal 53, Low Voltage = 0 Volt Terminal 53, High Voltage = 10 Volt Terminal 53, Low Ref./Feedback = 0 RPM Terminal 53, High Ref./Feedback = 1500 RPM...
How to Programme FC 300 Programming Guide 2 How to Programme 2.1 The Graphical and Numerical Local Control Panels The easiest programming of the frequency converter is performed by the Graphical LCP (LCP 102). It is necessary to consult the frequency converter Design Guide, when using the Numeric Local Control Panel (LCP 101).
How to Programme FC 300 Programming Guide 2.1.2 The LCD-Display Indicator lights (LEDs): The LCD-display has back light and a total of 6 alpha-numeric If certain threshold values are exceeded, the alarm and/or lines. The display lines show the direction of rotation (arrow), warning LED lights up.
Page 14
How to Programme FC 300 Programming Guide • It is possible to switch directly between Main Menu mode and [Hand on] - [Off] - [Auto on] Quick Menu mode. • Reset Parameter shortcut can be carried out by pressing down the •...
How to Programme FC 300 Programming Guide 2.1.3 Quick Transfer of Parameter Settings The parameter settings stored in the LCP are now transferred between Multiple Frequency Converters to the frequency converter indicated by the progress bar. When 100% is reached, press [OK].
Page 16
How to Programme FC 300 Programming Guide Status screen I: Operating variable: Unit: This read-out state is standard after start-up or initialization. Par. 16-00 Control Word Use [INFO] to obtain information about the measurement links Par. 16-01 Reference [Unit] [unit] to the displayed operating variables (1.1, 1.2, 1.3, 2 and 3).
How to Programme FC 300 Programming Guide 2.1.6 Parameter Set-Up Parameter Setting Par. 0-01 Language The frequency converter can be used for practically all assign- Par. 1-20 Motor Power [kW] [kW] ments, which is why the number of parameters is quite large.
Page 18
How to Programme FC 300 Programming Guide 2.1.8 Initial Commissioning The easiest way of carrying out the initial commissioning is by using the Quick Menu button and follow the quick set-up procedure using LCP 102 (read table from left to right). The example applies to open loop applications:...
How to Programme FC 300 Programming Guide 2.1.9 Main Menu Mode 2.1.11 Changing Data Start the Main Menu mode by pressing the [Main Menu] key. The procedure for changing data is the same whether you The read-out shown to the right appears on the display.
How to Programme FC 300 Programming Guide 2.1.14 Infinitely Variable Change of Numeric 2.1.17 How to Programme on the Numerical Data Value Local Control Panel If the chosen parameter represents a numeric data value, The following instructions are valid for the Numerical LCP (LCP ◀...
Page 21
How to Programme FC 300 Programming Guide Main Menu/ Quick Setup is used for programming all parame- ters or only the parameters in the Quick Meny (see also description of the LCP 102 earlier in this chapter). ▲ ▼ The parameter values can be changed using the [ ] keys when the value is flashing.
How to Programme FC 300 Programming Guide 2.1.18 Local Control Keys 2.1.19 Initialisation to Default Settings Keys for local control are found at the bottom of the LCP. Initialise the frequency converter to default settings in two ways: Recommended initialisation (via par. 14-22 Operation Mode) Select par.
3 Parameter Descriptions 18-** Readout 2 parameters 3.1 Parameter Selection 30-** Special Features Parameters for FC 300 are grouped into various par. groups for 32-** MCO Basic Settings parameters easy selection of the correct parameters for optimized operation of the frequency converter.
Page 24
Parameter Descriptions FC 300 Programming Guide 0-01 Language 0-03 Regional Settings Option: Function: Option: Function: Korean Part of Language package 2 Interna- Activates par. 1-20 Motor Power [kW] for setting tional the motor power in kW and sets the default...
Page 25
Option: Function: Select the set-up to control the frequency converter functions. Factory Cannot be changed. It contains the Danfoss setup data set, and can be used as a data source when returning the other set-ups to a known state. Set-up 1...
Page 26
Parameter Descriptions FC 300 Programming Guide 0-12 This Set-up Linked to 0-13 Readout: Linked Set-ups Option: Function: Array [5] 1. Change the edit set-up to Set-up 2 [2] in Range: Function: par. 0-11 Edit Set-up and set par. 0-12 This Set-up...
Page 27
Parameter Descriptions FC 300 Programming Guide 3.2.3 0-2* LCP Display 0-20 Display Line 1.1 Small Option: Function: Define the variables displayed in the Graphical Local Control [1610] Power [kW] Actual power consumed by the Panel. motor in kW. [1611] Power [hp]...
Page 28
Parameter Descriptions FC 300 Programming Guide 0-20 Display Line 1.1 Small 0-20 Display Line 1.1 Small Option: Function: Option: Function: [1639] Control Card Temperature of the control card. [1676] Analog In X30/12 Actual value at input X30/12 either as Temp.
Page 29
Parameter Descriptions FC 300 Programming Guide 0-20 Display Line 1.1 Small 0-20 Display Line 1.1 Small Option: Function: Option: Function: [3403] PCD 3 Write to [3459] Actual Master Velocity [3404] PCD 4 Write to [3460] Synchronizing Status [3405] PCD 5 Write to...
Page 30
Parameter Descriptions FC 300 Programming Guide Unit Type Speed Relation 0-25 My Personal Menu Dimensionless Linear Range: Function: Speed Applica- [0 - Define up to 50 parameters to appear in the Flow, volume tion 9999 ] Q1 Personal Menu, accessible via the [Quick...
Page 31
Parameter Descriptions FC 300 Programming Guide 0-30 Unit for User-defined Readout 0-39 Display Text 3 Option: Function: Range: Function: [125] ft3/s [0 - 0 ] Enter a text which can be viewed in the graphical display by selecting Display Text 3 [39] in par. 0-20, [126] ft3/min 0-21, 0-22, 0-23 or 0-24.
Page 32
Parameter Descriptions FC 300 Programming Guide 0-43 [Reset] Key on LCP 0-51 Set-up Copy Option: Function: Option: Function: Disabled No effect when [Reset] is pressed. Avoids No copy No function accidental alarm reset. Copy to set- Copies all parameters in the present Program-...
Parameter Descriptions FC 300 Programming Guide 0-65 Quick Menu Password Range: Function: 3.3 Parameters: 1-** Load and Motor [-9999 - Define the password for access to the Quick 3.3.1 1-0* General Settings 9999 ] Menu via the [Quick Menu] key. If par.
Page 34
Parameter Descriptions FC 300 Programming Guide 1-01 Motor Control Principle 1-01 Motor Control Principle Option: Function: Option: Function: Select which motor control principle to employ. Flux w/ very high accuracy speed and torque control, motor suitable for the most demanding applications. FC...
Page 35
Parameter Descriptions FC 300 Programming Guide 3.3.2 1-1* Motor Selection 1-04 Overload Mode Option: Function: This par. group cannot be adjusted while the motor is running. High torque Allows up to 160% over torque. 1-10 Motor Construction Normal torque For oversized motor - allows up to 110% over torque.
Page 36
Parameter Descriptions FC 300 Programming Guide 1-22 Motor Voltage 1-29 Automatic Motor Adaptation (AMA) Range: Function: Option: Function: Application [Application Enter the nominal motor voltage The AMA function optimises dynamic motor dependent dependant] according to the motor nameplate performance by automatically optimising the data.
Page 37
Parameter Descriptions FC 300 Programming Guide NOTE 1-31 Rotor Resistance (Rr) Avoid generating external torque during AMA. Range: Function: Applica- [Applica- Fine-tuning R will improve shaft perform- NOTE tion tion ance. Set the rotor resistance value using If one of the settings in par. 1-2* is changed,...
Page 38
Parameter Descriptions FC 300 Programming Guide The table shows the number of poles for normal speed ranges 1-35 Main Reactance (Xh) of various motor types. Define motors designed for other Range: Function: frequencies separately. The motor pole value is always an even...
Page 39
Parameter Descriptions FC 300 Programming Guide 1-51 Min Speed Normal Magnetising [RPM] 1-53 Model Shift Frequency Range: Function: Range: Function: Application [10 - 300 Set the required speed for normal depend- depend- ant] dependent RPM] magnetising current. If the speed is set lower than the motor slip speed, par.
Page 40
Parameter Descriptions FC 300 Programming Guide 1-55 U/f Characteristic - U 1-59 Flystart Test Pulses Frequency Range: Function: Range: Function: Application [0.0 - Enter the voltage at each frequency 200 % [0 - 500 Control the percentage of the frequency for the dependent 1000.0 V]...
Page 41
Parameter Descriptions FC 300 Programming Guide 1-62 Slip Compensation 1-66 Min. Current at Low Speed Range: Function: Range: Function: Applica- [-500 - Enter the % value for slip compensation, to depend- par. 4-17 Torque Limit Generator Mode automat- ant] ically adjust par. 1-66 Min. Current at Low Speed.
Page 42
Parameter Descriptions FC 300 Programming Guide 3.3.7 1-7* Start Adjustments 1-72 Start Function Option: Function: 1-71 Start Delay typically used in hoisting applications. Start Range: Function: speed/current in reference direction [4] is particu- larly used in applications with counterweight 0.0 s [0.0 - 10.0 s] This parameter refers to the start function...
Page 43
Parameter Descriptions FC 300 Programming Guide 1-75 Start Speed [Hz] 1-82 Min Speed for Function at Stop [Hz] Range: Function: Range: Function: Application [Applica- This par can be used for hoist applica- Application [Application Set the output frequency at dependent tion tions (cone rotor).
Page 44
Parameter Descriptions FC 300 Programming Guide 1-85 Precise Stop Speed Compensation Delay 1-90 Motor Thermal Protection Range: Function: Option: Function: 10 ms [0 - 100 Enter the delay time for sensors, PLCs, etc. for use in par. 1-83 Precise Stop Function. In...
Page 45
Parameter Descriptions FC 300 Programming Guide Using a digital input and 10 V as power supply: Example: The frequency converter trips when the motor temperature is too high. Parameter set-up: Set par. 1-90 Motor Thermal Protection to Thermistor Trip [2] Set par.
Page 46
Parameter Descriptions FC 300 Programming Guide 1-93 Thermistor Source Option: Function: Select the input to which the thermistor (PTC sensor) should be connected. An analog input option [1] or [2] cannot be selected if the analog input is already in use as a reference source (selected in par.
Parameter Descriptions FC 300 Programming Guide 3.4 Parameters: 2-** Brakes 2-03 DC Brake Cut In Speed [RPM] Range: Function: 3.4.1 2-0* DC-Brakes Application [Application Set the DC brake cut-in speed dependent dependant] for activation of the DC braking Par. group for configuring the DC brake and DC hold current set in par.
Page 48
Parameter Descriptions FC 300 Programming Guide 2-12 Brake Power Limit (kW) 2-15 Brake Check Range: Function: Option: Function: Application [Application Set the monitoring limit of the brake Select type of test and monitoring function to dependent dependant] power transmitted to the resistor.
Page 49
Parameter Descriptions FC 300 Programming Guide NOTE 2-19 Over-voltage Gain Remove a warning arising in connection with Off [0] or Range: Function: Warning [1] by cycling the mains supply. The fault must 100 % [0 - 200 %] Select over-voltage gain.
Page 50
Parameter Descriptions FC 300 Programming Guide 2-20 Release Brake Current 2-21 Activate Brake Speed [RPM] Range: Function: Range: Function: Applica- [Applica- Set the motor current for release of the Application [0 - 30000 Set the motor speed for activation of...
Page 51
Parameter Descriptions FC 300 Programming Guide 2-25 Brake Release Time 2-27 Torque Ramp Time Range: Function: Range: Function: 0.20 s [0.00 - 5.00 This value defines the time it takes for the 0.2 s [0.0 - 5.0 s] The value defines the duration of the torque mechanical brake to open.
Parameter Descriptions FC 300 Programming Guide 3.5 Parameters: 3-** Reference/Ramps 3-01 Reference/Feedback Unit Option: Function: [41] m/min Parameters for reference handling, definition of limitations, [45] and configuration of the reaction of the frequency converter [60] °C to changes. [70] mbar [71] 3.5.1 3-0* Reference Limits...
Page 53
Parameter Descriptions FC 300 Programming Guide 3-03 Maximum Reference Range: Function: Applica- [Applica- Enter the Maximum Reference. The tion tion Maximum Reference is the highest value depend- depend- obtainable by summing all references. ant] The Maximum Reference unit matches: •...
Page 54
Parameter Descriptions FC 300 Programming Guide 3-13 Reference Site 3-15 Reference Resource 1 Option: Function: Option: Function: Select which reference site to activate. Select the reference input to be used for the first reference signal. Linked to Use local reference when in Hand mode; or par.
Page 55
Parameter Descriptions FC 300 Programming Guide 3-17 Reference Resource 3 3-19 Jog Speed [RPM] Option: Function: Range: Function: Analog input 54 Application [Applica- Enter a value for the jog speed n dependent tion which is a fixed output speed. The...
Page 56
Parameter Descriptions FC 300 Programming Guide 3-40 Ramp 1 Type 3-45 Ramp 1 S-ramp Ratio at Accel. Start Option: Function: Range: Function: Select the ramp type, depending on require- 50 % [Application Enter the proportion of the total ramp-up ments for acceleration/deceleration.
Page 57
Parameter Descriptions FC 300 Programming Guide 3.5.4 3-5* Ramp 2 3-55 Ramp 2 S-ramp Ratio at Accel. Start Range: Function: Choosing ramp parameters, see 3-4*. 50 % [Application Enter the proportion of the total ramp-up dependant] time (par. 3-51 Ramp 2 Ramp up Time) in 3-50 Ramp 2 Type which the acceleration torque increases.
Page 58
Parameter Descriptions FC 300 Programming Guide 3-60 Ramp 3 Type 3-66 Ramp 3 S-ramp Ratio at Accel. End Option: Function: Range: Function: S-ramp S-ramp based on the values set in 50 % [Application Enter the proportion of the total ramp-up Const Time par.
Page 59
Parameter Descriptions FC 300 Programming Guide NOTE 3-76 Ramp 4 S-ramp Ratio at Accel. End If S-ramp [1] is selected and the reference during Range: Function: ramping is changed the ramp time may be prolonged in 50 % [Application Enter the proportion of the total ramp-up...
Page 60
Parameter Descriptions FC 300 Programming Guide 3-82 Quick Stop Ramp Type Option: Function: Select the ramp type, depending on requirements for acceleration and decelera- tion. A linear ramp will give constant acceleration during ramping. An S-ramp will give non-linear acceleration, compensating for jerk in the application.
Page 61
Parameter Descriptions FC 300 Programming Guide 3.5.8 3-9* Digital Pot.Meter 3-92 Power Restore Option: Function: The digital potentiometer function allows the user to increase Off Resets the Digital Potentiometer reference to 0% after or decrease the actual reference by adjusting the set-up of the power up.
Parameter Descriptions FC 300 Programming Guide 3.6 Parameters: 4-** Limits/Warnings 4-12 Motor Speed Low Limit [Hz] Range: Function: Application [Applica- Enter the minimum limit for motor 3.6.1 4-1* Motor Limits dependent tion speed. The Motor Speed Low Limit can dependant] be set to correspond to the minimum output frequency of the motor shaft.
Page 63
Parameter Descriptions FC 300 Programming Guide 4-16 Torque Limit Motor Mode 4-19 Max Output Frequency Range: Function: Range: Function: Application [Application This function limits the torque on 132.0 [1.0 - Provides a final limit on the output dependent dependant] the shaft to protect the mechanical 1000.0 Hz]...
Page 64
Parameter Descriptions FC 300 Programming Guide 4-21 Speed Limit Factor SourceOption Option: Function: Analog input 54 inv [10] Analog input X30-11 [12] Analog input X30-11 [14] Analog input X30-12 [16] Analog input X30-12 3.6.2 4-3* Motor Feedback Monitoring The par. group includes monitoring and handling of motor feedback devices as encoders, resolvers etc.
Page 65
Parameter Descriptions FC 300 Programming Guide 3.6.3 4-5* Adjustable Warnings 4-35 Tracking Error Range: Function: Use these parameters to adjust warning limits for current, 10 RPM [1 - 600 Enter the maximum permissible speed error speed, reference and feedback. Warnings that are shown on...
Page 66
Parameter Descriptions FC 300 Programming Guide 4-53 Warning Speed High 4-57 Warning Feedback High Range: Function: Range: Function: Applica- [Applica- Enter the n value. When the motor 999999.999 [Applica- Enter the upper feedback limit. HIGH tion tion speed exceeds this limit, the display...
Parameter Descriptions FC 300 Programming Guide 3.6.4 4-6* Speed Bypass 3.7 Parameters: 5-** Digital In/Out 3.7.1 5-0* Digital I/O Mode Some systems call for avoiding certain output frequencies or speeds, due to resonance problems in the system. A maximum of four frequency or speed ranges can be avoided.
Page 68
Digital input function Select Terminal No operation All *term 32, 33 FC 300 standard terminals are 18, 19, 27, 29, 32 and 33. MCB Reset 101 terminals are X30/2, X30/3 and X30/4. Coast inverse All *term 27 Terminal 29 functions as an output only in FC 302.
Page 69
Parameter Descriptions FC 300 Programming Guide Start (Default Digital input 18): Select start for a start/ 2 Ramp down Time) in the range 0 - par. 1-23 Motor stop command. Logic ‘1’ = start, logic ‘0’ = stop. Frequency. NOTE Latched The motor starts, if a pulse is applied for min.
Page 70
Parameter Descriptions FC 300 Programming Guide [31] Pulse Edge triggered pulse input counts number of [60] Counter A (Terminal 29 or 33 only) Input for increment edge pulse flanks per sample time. This gives a higher counting in the SLC counter.
Page 71
Parameter Descriptions FC 300 Programming Guide 5-13 Terminal 29 Digital Input 5-19 Terminal 37 Safe Stop Option: Function: Option: Function: Select the function from the available digital input PTC 1 Alarm Coasts frequency converter when safe stop is range and the additional options [60], [61], [63] and activated.
Page 72
Parameter Descriptions FC 300 Programming Guide NOTE 5-23 Terminal X46/7 Digital Input When Auto Reset/ Warning is selected the frequency Option: Function: converter opens up for automatic restart. No operation This parameter is active when option moduleMCB 113 is installed in the frequency Overview of functions, alarms and warnings converter.
Page 73
Parameter Descriptions FC 300 Programming Guide Run in range / Motor is running within the programmed [27] Torque limit Use in performing a coasting stop and in no warning current and speed ranges set in and stop torque limit condition. If the frequency par.
Page 74
Parameter Descriptions FC 300 Programming Guide [63] Comparator 3 See par. group 13-1*. If Comparator 3 is [85] SL Digital See par. 13-52 SL Controller Action. The input evaluated as TRUE, the output will go high. Output F will go high whenever the Smart Logic Otherwise, it will be low.
Page 75
Parameter Descriptions FC 300 Programming Guide 5-31 Terminal 29 Digital Output 5-32 Term X30/6 Digi Out (MCB 101) Option: Function: Option: Function: No operation Functions are described under 5-3* Digital [47] Bus ctrl, 0 if timeout Outputs [51] MCO controlled...
Page 76
Parameter Descriptions FC 300 Programming Guide 3.7.4 5-4* Relays 5-33 Term X30/7 Digi Out (MCB 101) Option: Function: Parameters for configuring the timing and the output [17] Above speed, high functions for the relays. [18] Out of feedb. range [19]...
Page 80
Parameter Descriptions FC 300 Programming Guide 5-52 Term. 29 Low Ref./Feedb. Value Range: Function: 0.000 [-999999.999 - Enter the low reference value limit Reference- 999999.999 for the motor shaft speed [RPM]. FeedbackU- ReferenceFeed- This is also the lowest feedback backUnit] value, see also par.
Page 81
Parameter Descriptions FC 300 Programming Guide Options for readout output variables: 5-57 Term. 33 Low Ref./Feedb. Value Range: Function: Parameters for configuring the 0.000 N/A [-999999.999 - Enter the low reference value scaling and output functions of 999999.999 N/A] [RPM] for the motor shaft speed.
Page 82
Parameter Descriptions FC 300 Programming Guide 5-62 Pulse Output Max Freq #27 5-66 Terminal X30/6 Pulse Output Variable Range: Function: Select the variable for read-out on terminal X30/6. This parameter cannot be adjusted while the motor is running. Application [0 - 32000...
Page 83
Parameter Descriptions FC 300 Programming Guide 3.7.7 5-7* 24 V Encoder Input Connect the 24 V encoder to terminal 12 (24 V DC supply), terminal 32 (Channel A), terminal 33 (Channel B), and terminal 20 (GND). The digital inputs 32/33 are active for encoder inputs when 24 V encoder is selected in par.
Page 84
Parameter Descriptions FC 300 Programming Guide 3.7.8 5-9* Bus Controlled 5-95 Pulse Out #29 Bus Control Range: Function: This par. group selects digital and relay outputs via a fieldbus 0.00 % [0.00 - Set the output frequency transferred to the setting.
Parameter Descriptions FC 300 Programming Guide 3.8 Parameters: 6-** Analog In/Out 6-01 Live Zero Timeout Function Option: Function: 3.8.1 6-0* Analog I/O Mode [21] Coast and trip The analog inputs can freely be allocated to be either voltage (FC 301: 0..10 V, FC 302: 0..+/- 10V) or current (FC 301/FC 302: 3.8.2 6-1* Analog Input 1...
Page 86
Parameter Descriptions FC 300 Programming Guide 6-13 Terminal 53 High Current 6-21 Terminal 54 High Voltage Range: Function: Range: Function: 20.00 mA [Application Enter the high current value 10.00 V [Application Enter the high voltage value. This dependant] corresponding to the high reference/...
Page 87
Parameter Descriptions FC 300 Programming Guide 3.8.4 6-3* Analog Input 3 MCB 101 3.8.5 6-4* Analog Input 4 MCB 101 Par. group for configuring the scale and limits for analog input Par. group for configuring the scale and limits for analog input 3 (X30/11) placed on option module MCB 101.
Page 88
Parameter Descriptions FC 300 Programming Guide 3.8.6 6-5* Analog Output 1 6-50 Terminal 42 Output Option: Function: Parameters for configuring the scaling and limits for analog [113] PID output 1, i.e. Terminal 42. Analog outputs are current outputs: Clamped 0/4 – 20 mA. Common terminal (terminal 39) is the same...
Page 89
Parameter Descriptions FC 300 Programming Guide 6-50 Terminal 42 Output Option: Function: [142] Bus ctrl Par. 4-54 Warning Reference Low defines the 4-20mA behaviour of the analog output in case of bus t.o. time-out. [149] Torque % Analogue output at zero torque = 12 mA.
Page 90
Parameter Descriptions FC 300 Programming Guide 3.8.7 6-6* Analog Output 2 MCB 101 6-60 Terminal X30/8 Output Option: Function: Analog outputs are current outputs: 0/4 - 20 mA. Common [119] Torque % terminal (terminal X30/8) is the same terminal and electrical potential for analog common connection.
Page 92
Parameter Descriptions FC 300 Programming Guide 6-70 Terminal X45/1 Output 6-70 Terminal X45/1 Output Option: Function: Option: Function: [107] Speed Taken from par. 3-03 Maximum Reference. 20 mA [150] Max Out In relation to par. 4-19 Max Output Frequency. 0-20 mA = value in par.
Page 93
Parameter Descriptions FC 300 Programming Guide 6-74 Terminal X45/1 Output Timeout Preset 6-82 Terminal X45/3 Output Max Scale Range: Function: Option: Function: I RANGE mA 0.00% [0.00 - Holds the preset level of Analog Output 3 100 % I DESIRED MAX mA 100.00%]...
Parameter Descriptions FC 300 Programming Guide 3.9 Parameters: 7-** Controllers 7-03 Speed PID Integral Time Range: Function: 3.9.1 7-0* Speed PID Ctrl. Applica- [2.0 - Enter the speed controller integral time, tion 20000.0 which determines the time the internal PID...
Page 95
Parameter Descriptions FC 300 Programming Guide 7-06 Speed PID Lowpass Filter Time Range: Function: Applica- [1.0 - Set a time constant for the speed control tion 100.0 low-pass filter. The low-pass filter improves depend- steady-state performance and dampens oscillations on the feedback signal. This is an advantage if there is a great amount on noise in the system, see illustration below.
Page 96
Parameter Descriptions FC 300 Programming Guide 7-07 Speed PID Feedback Gear Ratio 7-20 Process CL Feedback 1 Resource Range: Function: Option: Function: 1.0000 [Application dependant] of the first of these signals. The second input signal is defined in par. 7-22 Process CL Feedback 2 Resource.
Page 97
Parameter Descriptions FC 300 Programming Guide 7-32 Process PID Start Speed 7-38 Process PID Feed Forward Factor Range: Function: Range: Function: 0 RPM [0 - 6000 Enter the motor speed to be attained as a start changing the set point. par. 7-38 Process PID Feed Forward Factor is active when par.
Page 98
Parameter Descriptions FC 300 Programming Guide 3.9.6 7-5* Process PID Ctrl. 7-45 Process PID Feed Fwd Resource Option: Function: 7-50 Process PID Extended PID No function Select which drive input should be Option: Function: used as the feed forward factor. The FF...
Parameter Descriptions FC 300 Programming Guide 3.10 Parameters: 8-** Communications 8-04 Control Word Timeout Function Select the time-out function. The time-out function activates when and Options the control word fails to be updated within the time period specified in par. 8-03 Control Word Timeout Time.
Page 100
Parameter Descriptions FC 300 Programming Guide 8-06 Reset Control Word Timeout 8-07 Diagnosis Trigger Option: Function: This parameter is active only when Hold set-up [0] has been selected in par. 8-05 End-of-Timeout Function. 14 - 17 VLT VLT status word par.
Page 101
Parameter Descriptions FC 300 Programming Guide 3.10.2 8-1* Ctrl. Word Settings 8-13 Configurable Status Word STW Option: Function: 8-10 Control Word Profile [61] Comparator 1 If Comparator 1 is evaluated as TRUE, the input will go high. Otherwise, it will be low.
Page 102
Parameter Descriptions FC 300 Programming Guide 8-14 Configurable Control Word CTW 8-35 Minimum Response Delay Option: Function: Range: Function: Selection of control word bit 10 if it is 10 ms [Application Specify the minimum delay time active low or active high...
Page 103
Parameter Descriptions FC 300 Programming Guide 8-41 Parameters for signals 8-41 Parameters for signals Option: Function: Option: Function: None This parameter [1616] Torque [Nm] contains a list of [1617] Speed [RPM] signals available for [1618] Motor Thermal selection in [1619] KTY sensor temperature par.
Page 104
Parameter Descriptions FC 300 Programming Guide 8-41 Parameters for signals 8-42 PCD write configuration Option: Function: Option: Function: [3311] Synchronization Factor Slave (M:S) the selected parame- ters as data values. [3401] PCD 1 Write to MCO [3402] PCD 2 Write to MCO...
Page 105
Parameter Descriptions FC 300 Programming Guide 8-43 PCD read configuration 8-43 PCD read configuration Option: Function: Option: Function: None Select the parameters to be [1667] Freq. Input #29 [Hz] assigned to PCD's of the [1668] Freq. Input #33 [Hz] telegrams. The number of...
Page 106
Parameter Descriptions FC 300 Programming Guide 3.10.5 8-5* Digital/Bus 8-53 Start Select Option: Function: Parameters for configuring the control word Digital/Bus Select control of the frequency converter start merging. function via the terminals (digital input) and/or via the fieldbus. NOTE Digital Activates Start command via a digital input.
Page 107
Parameter Descriptions FC 300 Programming Guide 3.10.6 8-8* FC Port Diagnostics 8-56 Preset Reference Select Option: Function: These parameters are used for monitoring the Bus communi- Select control of the frequency converter Preset cation via the Port. Reference selection via the terminals (digital input) and/or via the fieldbus.
Parameter Descriptions FC 300 Programming Guide 3.11 Parameters: 9-** Profibus 9-15 PCD Write Configuration Array [10] 9-00 Setpoint Option: Function: Range: Function: [663] Terminal X30/8 Bus Control [0 - 65535 ] This parameter receives cyclical reference from a [673] Terminal X45/1 Bus Control Master Class 2.
Page 109
Parameter Descriptions FC 300 Programming Guide 9-16 PCD Read Configuration 9-16 PCD Read Configuration Array [10] Array [10] Option: Function: Option: Function: [1610] Power [kW] [1694] Ext. Status Word [1611] Power [hp] [1860] Digital Input 2 [1612] Motor Voltage [3421] PCD 1 Read from MCO...
Page 110
Parameter Descriptions FC 300 Programming Guide 9-22 Telegram Selection 9-23 Parameters for Signals Displays the Profibus telegram configuration. Array [1000] Read only Option: Function: Option: Function: [105] PPO 5 [1600] Control Word [106] PPO 6 [1601] Reference [Unit] [107] PPO 7...
Page 111
Parameter Descriptions FC 300 Programming Guide 9-23 Parameters for Signals 9-23 Parameters for Signals Array [1000] Array [1000] Read only Read only Option: Function: Option: Function: [1678] Analog Out X45/1 [mA] [3461] Axis Status [1679] Analog Out X45/3 [mA] [3462] Program Status...
Page 112
Parameter Descriptions FC 300 Programming Guide 9-47 Fault Number 9-63 Actual Baud Rate Range: Function: Option: Function: [0 - 0 ] This buffer contains the alarm number (e.g. 2 for live 6000 kbit/s zero error, 4 for mains phase loss) for all alarms and...
Page 113
Parameter Descriptions FC 300 Programming Guide 9-71 Profibus Save Data Values 9-82 Defined Parameters (3) Option: Function: Array [116] No LCP access Parameter values changed via Profibus are not Read only automatically stored in non-volatile memory. Use this parameter to activate a function that stores...
ODVA, par. 10-10 Process Data Type Selection NOTE options [2] and [3] are available. The options depend on installed option. Instances 100/150 and 101/151 are Danfoss- specific. Instances 20/70 and 21/71 are ODVA- 10-01 Baud Rate Select specific AC Drive profiles.
Page 115
Parameter Descriptions FC 300 Programming Guide 10-11 Process Data Config Write 10-12 Process Data Config Read Select the process write data for I/O Assembly Instances 101/151. Select the process read data for I/O Assembly Instances 101/151. Elements [2] and [3] of this array can be selected. Elements [0] and Elements [2] and [3] of this array can be selected.
Page 116
Parameter Descriptions FC 300 Programming Guide 10-12 Process Data Config Read 10-13 Warning Parameter Range: Function: Select the process read data for I/O Assembly Instances 101/151. Elements [2] and [3] of this array can be selected. Elements [0] and [0 - View a DeviceNet-specific Warning word.
Page 117
Parameter Descriptions FC 300 Programming Guide 3.12.3 10-2* COS Filters 10-31 Store Data Values Option: Function: 10-20 COS Filter 1 Store all Stores all parameter values for all set-ups in the Range: Function: setups non-volatile memory. The selection returns to Off [0] when all parameter values have been stored.
Parameter Descriptions FC 300 Programming Guide 3.13 Parameters: 12-** Ethernet 12-08 Host Name Range: Function: 3.13.1 12-0* IP Settings Blank [0-19 characters] Logical (given) name of option. 12-09 Physical Address 12-00 IP Address Assignment Range: Function: Option: Function: [00:1B:08:00:00:00 – 00:1B: Read only Displays the Physical Selects the IP Address assignment method.
Page 119
Parameter Descriptions FC 300 Programming Guide 3.13.3 12-2* Process Data 3.13.4 12-3* EtherNet/IP 12-20 Control Instance 12-30 Warning Parameter Range: Function: Range: Function: [None, 20, 21, 100, Read only. Displays the originator-to-target [0000 – Read only. Displays the EtherNet/IP specific 16-bit 101, 103] connection point.
Page 120
Parameter Descriptions FC 300 Programming Guide 3.13.6 12-9* Advanced Ethernet Settings 12-37 COS Inhibit Timer Range: Function: 12-90 Cable Diagnostics [0 – 65.535 Read only Change-Of-State inhibit timer. If the option is configured for COS operation, this inhibit Option: Function: timer can be configured in the Forward Open Enables/disables advanced Cable diagnosis function.
Page 121
Parameter Descriptions FC 300 Programming Guide 12-94 Broadcast Storm Protection 12-98 Interface Counters Option: Function: Option: Function: The built-in switch is capable of protecting the Read only. Advanced Interface switch system from receiving too many counters, from build-in switch, can...
Parameter Descriptions FC 300 Programming Guide 3.14.2 13-0* SLC Settings 3.14 Parameters: 13-** Smart Logic Control Use the SLC settings to activate, deactivate and reset the Smart Logic Control sequence. The logic functions and 3.14.1 Prog. Features comparators are always running in the background, which opens for separate control of digital inputs and outputs.
Page 123
Parameter Descriptions FC 300 Programming Guide 13-01 Start Event 13-01 Start Event Option: Function: Option: Function: Feedback Low and par. 4-57 Warning [37] Digital input Digital input DI32 [37] Use the result of Feedback High. DI32 digital input 32. [14] Below feedb.
Page 124
Parameter Descriptions FC 300 Programming Guide 13-02 Stop Event 13-02 Stop Event Select the boolean (TRUE or FALSE) input to activate Smart Logic Select the boolean (TRUE or FALSE) input to activate Smart Logic Control. Control. Option: Function: Option: Function: [15] Above feedb.
Page 125
Parameter Descriptions FC 300 Programming Guide 13-10 Comparator Operand 13-10 Comparator Operand Array [6] Array [6] Option: Function: Option: Function: Motor torque Motor torque [5] [Nm] clockwise (the logical product of the status bits “running” AND “reverse”) Motor power Motor power [6] [kW] or [hp]...
Page 126
Parameter Descriptions FC 300 Programming Guide 13-10 Comparator Operand 13-10 Comparator Operand Array [6] Array [6] Option: Function: Option: Function: [80] Thermal Thermal warning [80] The thermal warning [122] SL Time-out 2 SL Time-out 2 [122] The result of SLC timer...
Page 127
Parameter Descriptions FC 300 Programming Guide 13-10 Comparator Operand 13-11 Comparator Operator Array [6] Array [6] Option: Function: Option: Function: Linked to hand/auto, while the LCP is in Select the operator to be used in the compari- Auto on mode.
Page 128
Parameter Descriptions FC 300 Programming Guide 3.14.4 13-2* Timers 13-40 Logic Rule Boolean 1 Array [6] Use the result (TRUE or FALSE) from timers directly to define an Option: Function: event (see par. 13-51 SL Controller Event), or as boolean input in Current limit a logic rule (see par.
Page 129
Parameter Descriptions FC 300 Programming Guide 13-40 Logic Rule Boolean 1 13-42 Logic Rule Boolean 2 Array [6] Array [6] Option: Function: Option: Function: [74] SL Time-out 7 False Select the second boolean (TRUE or FALSE) input for the selected logic [75] Start command given rule.
Page 130
Parameter Descriptions FC 300 Programming Guide 13-42 Logic Rule Boolean 2 13-44 Logic Rule Boolean 3 Array [6] Array [6] Option: Function: Option: Function: [47] Up key False Select the third boolean (TRUE or FALSE) input for the selected logic [48] Down key rule.
Page 131
Parameter Descriptions FC 300 Programming Guide 13-44 Logic Rule Boolean 3 13-51 SL Controller Event Array [6] Array [20] Option: Function: Option: Function: [47] Up key [17] Mains out of range [48] Down key [18] Reversing [50] Comparator 4 [19] Warning...
Page 132
Parameter Descriptions FC 300 Programming Guide 13-51 SL Controller Event 13-52 SL Controller Action Array [20] Array [20] Option: Function: Option: Function: [85] Digital input x46/13 commands coming from either the digital inputs or via a fieldbus. 13-52 SL Controller Action [13] Select preset Select preset reference 3 [13] –...
4-11 Motor Speed Low Limit [RPM] until the motor is as noiseless as possible. See also 14-00 Switching Pattern par. 14-00 Switching Pattern and the section Special conditions in the VLT AutomationDrive FC 300 Design Option: Function: Guide.
Page 135
Parameter Descriptions FC 300 Programming Guide 3.15.2 14-1* Mains On/Off 14-10 Mains Failure Par. 14-10 Mains Failure is typically used where very short mains Parameters for configuring mains failure monitoring and interruptions (voltage dips) are present. At 100% load and a short handling.
Page 136
Mains Voltage at Mains Fault is the will ramp the motor up to the reference same for VLT 5000 and FC 300, the speed (if the mains interruption is detection level is different. Use the...
Page 137
Parameter Descriptions FC 300 Programming Guide NOTE 14-14 Kin. Backup Time Out Automatic reset will also be active for resetting safe stop Range: Function: function in firmware version < 4.3x. 60 s [0 - 60 s] This parameter defines the Kinetic Backup Time...
Page 138
Parameter Descriptions FC 300 Programming Guide 14-22 Operation Mode 14-25 Trip Delay at Torque Limit Option: Function: Range: Function: on. Test plugs (connect the following terminals 60 s [0 - 60 Enter the torque limit trip delay in seconds. When to each other): 18 - 27 - 32;...
Page 139
Parameter Descriptions FC 300 Programming Guide 14-30 Current Lim Ctrl, Proportional Gain 14-42 Minimum AEO Frequency Range: Function: Range: Function: 100 % [0 - 500 %] Enter the proportional gain value for the 10 Hz [5 - 40 Hz] Enter the minimum frequency at which the current limit controller.
Page 140
Option: Function: The parameters in this group are for setting of compatibility Select which reaction the frequency converter for VLT 3000, VLT 5000 to FC 300 should take in case a fan fault is detected. 14-72 VLT Alarm Word Disabled...
Page 141
Parameter Descriptions FC 300 Programming Guide 14-90 Fault Level Option: Function: Use this parameter to customize Fault levels. Use [0] "Off" with caution as it will ignore all Warnings & Alarms for the chosen source. Warning Trip Trip Lock Failure...
Parameter Descriptions FC 300 Programming Guide NOTE 3.16 Parameters: 15-** Drive Informa- The reset is carried out by pressing [OK]. tion 15-07 Reset Running Hours Counter 3.16.1 15-0* Operating Data Option: Function: Do not reset 15-00 Operating Hours Reset Select Reset [1] and press [OK] to reset the...
Page 143
Parameter Descriptions FC 300 Programming Guide 15-10 Logging Source 15-12 Trigger Event Array [4] Select the trigger event. When the trigger event occurs, a window is applied to freeze the log. The log will then retain a specified Option: Function:...
Page 144
Parameter Descriptions FC 300 Programming Guide 3.16.3 15-2* Historic Log 15-21 Historic Log: Value Array [50] View up to 50 logged data items via the array parameters in Range: Function: this par. group. For all parameters in the group, [0] is the most Digtal input Decimal value.
Page 145
Range: Function: ordering the frequency converter in its [0 - 255 ] View the error code and look up its meaning in the original configuration. Troubleshooting chapter of the FC 300 Design Guide. 15-45 Actual Typecode String Range: Function: 15-31 Alarm Log: Value...
Parameter Descriptions FC 300 Programming Guide 3.16.6 15-6* Option Ident. 3.17 Parameters: 16-** Data Read-outs This read-only par. group contains information about the hardware and software configuration of the options installed 3.17.1 16-0* General Status in slots A, B C0 and C1.
Page 147
Parameter Descriptions FC 300 Programming Guide 3.17.2 16-1* Motor Status 16-16 Torque [Nm] Range: Function: 16-10 Power [kW] [-3000.0 - View the torque value with sign, applied to the Range: Function: 3000.0 motor shaft. Linearity is not exact between 160% motor current and torque in relation to 0.00...
Page 148
Parameter Descriptions FC 300 Programming Guide 16-25 Torque [Nm] High 16-37 Inv. Max. Current Range: Function: Range: Function: [-200000000.0 - View the torque value with sign, applied Application [0.01 - View the inverter maximum 200000000.0 to the motor shaft. Some motors supply dependent 10000.00 A]...
Page 149
Parameter Descriptions FC 300 Programming Guide 16-52 Feedback [Unit] 16-60 Digital Input Range: Function: Range: Function: 0.000 [-999999.999 - View the feedback unit resulting Reference- 999999.999 from the selection of unit and FeedbackU- ReferenceFeed- scaling in par. 3-00 Reference backUnit] Range, par.
Page 150
Parameter Descriptions FC 300 Programming Guide 16-66 Digital Output [bin] 16-73 Counter B Range: Function: Range: Function: [0 - 15 ] View the binary value of all digital outputs. [-2147483648 - View the present value of Counter B. 2147483647 ]...
Page 151
Parameter Descriptions FC 300 Programming Guide 3.17.6 16-8* Fieldbus & FC Port 3.17.7 16-9* Diagnosis Read-Outs Parameters for reporting the BUS references and control 16-90 Alarm Word words. Range: Function: 16-80 Fieldbus CTW 1 0 N/A [0 - 4294967295 N/A] View the alarm word sent via the...
Page 152
Parameter Descriptions FC 300 Programming Guide 3.18 Parameters: 17-** Motor Feedb. 17-24 SSI Data Length Range: Function: Option [13 - 25 ] Set the number of bits for the SSI telegram. Additional parameters to configure the Encoder (MCB 102) or Choose 13 bits for single-turn encoders and 25 the Resolver (MCB 103) Feedback Option.
Page 153
Parameter Descriptions FC 300 Programming Guide 3.18.3 17-5* Resolver Interface 17-59 Resolver Interface Activate the MCB 103 resolver option when the resolver parame- Par. group 17-5* is used for setting parameters for the MCB ters are selected. 103 Resolver Option.
Parameter Descriptions FC 300 Programming Guide 3.19 Parameters: 18-** Data Readouts 2 3.20 Parameters: 30-** Special Features 3.20.1 30-0* Wobble Function 18-36 Analog Input X48/2 [mA] Range: Function: The wobble function is primarily used for synthetic yarn 0.000 [-20.000 - 20.000 ] View the actual current measured at winding applications.
Page 155
Parameter Descriptions FC 300 Programming Guide NOTE 30-04 Wobble Jump Frequency [Hz] This parameter can be set while running. Range: Function: parameter can only be changed in stop- NOTE mode The setting of “Center Frequency” takes place via the normal reference handling parameters, 3-1*...
Page 156
Parameter Descriptions FC 300 Programming Guide 30-19 Wobble Delta Freq. Scaled 30-83 Speed PID Proportional Gain Range: Function: Range: Function: 0.0 Hz [0.0 - 1000.0 Hz] Readout parameter. View the actual Application [0.0000 - Enter the speed controller propor- wobble delta frequency after scaling dependent 1.0000 ]...
Parameter Descriptions FC 300 Programming Guide 3.21 Parameters: 35-** Sensor Input 35-06 Temperature Sensor Alarm Function Select the alarm function: Option Option: Function: 3.21.1 35-0* Temp. Input Mode (MCB 114) Stop Stop and trip 35-00 Term. X48/4 Temp. Unit 3.21.2 35-1* Temp. Input X48/4 (MCB 114)
Page 158
Parameter Descriptions FC 300 Programming Guide 35-25 Term. X48/7 Temp. Monitor 35-37 Term. X48/10 High Temp. Limit Range: Function: This parameter gives the possibility of enabling or disabling the temperature monitor for terminal X48/7. The temperature limits Application [Application Enter the maximum tempera- can be set in par.
Parameter Lists FC 300 Programming Guide 4-Set-up 4 Parameter Lists 'All set-ups': the parameter can be set individually in each of the four set-ups, i. e. one single parameter can have four different data values. FC Series ’1 set-up’: data value will be the same in all set-ups.
Page 160
Parameter Lists FC 300 Programming Guide 4.1.1 0-** Operation/Display Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion index operation 0-0* Basic Settings 0-01 Language [0] English 1 set-up TRUE Uint8 0-02 Motor Speed Unit...
Page 161
Parameter Lists FC 300 Programming Guide 4.1.2 1-** Load/Motor Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 1-0* General Settings 1-00 Configuration Mode null All set-ups TRUE Uint8 1-01 Motor Control Principle...
Page 162
Parameter Lists FC 300 Programming Guide Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 1-68 Minimum Inertia All set-ups FALSE Uint32 1-69 Maximum Inertia All set-ups FALSE Uint32 1-7* Start Adjustments...
Page 163
Parameter Lists FC 300 Programming Guide 4.1.3 2-** Brakes Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 2-0* DC-Brake 2-00 DC Hold Current 50 % All set-ups TRUE Uint8 2-01...
Page 164
Parameter Lists FC 300 Programming Guide 4.1.4 3-** Reference/Ramps Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 3-0* Reference Limits 3-00 Reference Range null All set-ups TRUE Uint8 3-01 Reference/Feedback Unit...
Page 165
Parameter Lists FC 300 Programming Guide Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 3-8* Other Ramps 3-80 Jog Ramp Time All set-ups TRUE Uint32 3-81 Quick Stop Ramp Time...
Page 166
Parameter Lists FC 300 Programming Guide 4.1.5 4-** Limits / Warnings Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 4-1* Motor Limits 4-10 Motor Speed Direction null All set-ups FALSE...
Page 167
Parameter Lists FC 300 Programming Guide 4.1.6 5-** Digital In/Out Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 5-0* Digital I/O mode 5-00 Digital I/O Mode [0] PNP All set-ups...
Page 168
Parameter Lists FC 300 Programming Guide Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 5-66 Terminal X30/6 Pulse Output Variable null All set-ups TRUE Uint8 5-68 Pulse Output Max Freq #X30/6...
Page 169
Parameter Lists FC 300 Programming Guide 4.1.7 6-** Analog In/Out Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 6-0* Analog I/O Mode 6-00 Live Zero Timeout Time 10 s All set-ups...
Page 170
Parameter Lists FC 300 Programming Guide Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 6-74 Terminal X45/1 Output Timeout Preset 0.00 % 1 set-up TRUE Uint16 6-8* Analog Output 4...
Page 171
Parameter Lists FC 300 Programming Guide 4.1.8 7-** Controllers Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 7-0* Speed PID Ctrl. 7-00 Speed PID Feedback Source null All set-ups FALSE...
Page 172
Parameter Lists FC 300 Programming Guide 4.1.9 8-** Comm. and Options Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 8-0* General Settings 8-01 Control Site [0] Digital and ctrl.word All set-ups...
Page 173
Parameter Lists FC 300 Programming Guide 4.1.10 9-** Profibus Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 9-00 Setpoint 0 N/A All set-ups TRUE Uint16 9-07 Actual Value 0 N/A...
Page 174
Parameter Lists FC 300 Programming Guide 4.1.11 10-** CAN Fieldbus Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 10-0* Common Settings 10-00 CAN Protocol null 2 set-ups FALSE Uint8 10-01 Baud Rate Select...
Page 175
Parameter Lists FC 300 Programming Guide 4.1.12 12-** Ethernet Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion index operation 12-0* IP Settings 12-00 IP Address Assignment null 2 set-ups TRUE Uint8 12-01 IP Address...
Page 176
Parameter Lists FC 300 Programming Guide Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion index operation 12-8* Other Ethernet Services 12-80 FTP Server [0] Disabled 2 set-ups TRUE Uint8 12-81 HTTP Server...
Page 177
Parameter Lists FC 300 Programming Guide 4.1.14 14-** Special Functions Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion index operation 14-0* Inverter Switching 14-00 Switching Pattern null All set-ups TRUE Uint8 14-01 Switching Frequency...
Page 178
Parameter Lists FC 300 Programming Guide Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion index operation 14-7* Compatibility 14-72 Legacy Alarm Word 0 N/A All set-ups FALSE Uint32 14-73 Legacy Warning Word...
Page 179
Parameter Lists FC 300 Programming Guide 4.1.15 15-** Drive Information Par. No. Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 15-0* Operating Data 15-00 Operating Hours All set-ups FALSE Uint32 15-01 Running Hours...
Page 180
Parameter Lists FC 300 Programming Guide Par. No. Parameter description Default value 4-set-up FC 302 Change Conver- Type only during sion index operation 15-74 Option in Slot C0 0 N/A All set-ups FALSE VisStr[30] 15-75 Slot C0 Option SW Version...
Page 181
Parameter Lists FC 300 Programming Guide 4.1.16 16-** Data Readouts Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 16-0* General Status 16-00 Control Word 0 N/A All set-ups FALSE 0.000 ReferenceFeedbackU-...
Page 182
Parameter Lists FC 300 Programming Guide Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 16-65 Analog Output 42 [mA] 0.000 N/A All set-ups FALSE Int16 16-66 Digital Output [bin] 0 N/A...
Page 183
Parameter Lists FC 300 Programming Guide 4.1.17 17-** Motor Feedb.Option Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 17-1* Inc. Enc. Interface 17-10 Signal Type [1] RS422 (5V TTL) All set-ups...
Page 184
Parameter Lists FC 300 Programming Guide 4.1.18 18-** Data Readouts 2 Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 18-3* Analog Readouts 18-36 Analog Input X48/2 [mA] 0.000 N/A All set-ups...
Page 185
Parameter Lists FC 300 Programming Guide 4.1.20 32-** MCO Basic Settings Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 32-0* Encoder 2 32-00 Incremental Signal Type [1] RS422 (5V TTL)
Page 186
Parameter Lists FC 300 Programming Guide Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion index operation 32-8* Velocity & Accel. 32-80 Maximum Velocity (Encoder) 1500 RPM 2 set-ups TRUE Uint32 32-81 Shortest Ramp 1.000 s...
Page 187
Parameter Lists FC 300 Programming Guide Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 33-46 Target Window LimitValue 1 N/A 2 set-ups TRUE Uint16 33-47 Size of Target Window 0 N/A...
Page 188
Parameter Lists FC 300 Programming Guide 4.1.22 34-** MCO Data Readouts Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 34-0* PCD Write Par. 34-01 PCD 1 Write to MCO 0 N/A...
Page 189
Parameter Lists FC 300 Programming Guide 4.1.23 35-** Sensor Input Option Par. Parameter description Default value 4-set-up FC 302 Change Conver- Type No. # only during sion operation index 35-0* Temp. Input Mode 35-00 Term. X48/4 Temp. Unit [60] °C...
Troubleshooting FC 300 Programming Guide If an alarm cannot be reset, the reason may be that its cause 5 Troubleshooting has not been rectified, or the alarm is trip-locked (see also table on following page). 5.1.1 Warnings/Alarm Messages Alarms that are trip-locked offer additional protection,...
Page 191
Troubleshooting FC 300 Programming Guide No. Description Warning Alarm/Trip Alarm/Trip Lock Parameter Reference 10 Volts low Live zero error Par. 6-01 Live Zero Timeout Function No motor Par. 1-80 Function at Stop Mains phase loss Par. 14-12 Function at Mains Imbalance...
Page 192
Troubleshooting FC 300 Programming Guide A trip is the action when an alarm has appeared. The trip will LED indication coast the motor and can be reset by pressing the reset button Warning yellow or make a reset by a digital input (par. group 5-1* [1]). The...
Page 193
Troubleshooting FC 300 Programming Guide The alarm words, warning words and extended status words Alarm/warning limits: can be read out via serial bus or optional fieldbus for 3 x 200 - 240 V 3 x 380 - 500 V 3 x 525 - 600 V diagnose.
Page 194
Troubleshooting FC 300 Programming Guide WARNING/ALARM 13, Over Current: than 90%. If Trip [2] has been selected in par. 2-13 Brake Power The inverter peak current limit (approx. 200% of the rated Monitoring, the frequency converter cuts out and issues this current) is exceeded.
Page 195
ALARM 38, Internal fault: 5125 Option in slot C0: Hardware incompatible with Control By this alarm it may be necessary to contact your Danfoss board hardware supplier. Some typical alarm messages: 5126 Option in slot C1: Hardware incompatible with Control board hardware 0 The serial port cannot be initialized.
Page 196
Troubleshooting FC 300 Programming Guide WARNING 49, Speed limit: ALARM 63, Mechanical Brake Low: The speed is not within the specified range in par. 4-11 Motor The actual motor current has not exceeded the “release brake” Speed Low Limit [RPM] and par. 4-13 Motor Speed High Limit current within the “Start delay”...
Page 197
Troubleshooting FC 300 Programming Guide ALARM 72, Dangerous Failure: ALARM 79, Illegal power section configuration Safe Stop with Trip Lock. The Dangerous Failure Alarm is The scaling card is the incorrect part number or not installed. issued if the combination of safe stop commands is unexpec- Also MK102 connector on the power card could not be instal- ted.
Page 198
Troubleshooting FC 300 Programming Guide ALARM 246, Power card supply This alarm is only for F Frame drives. It is equivalent to Alarm 46. The report value in the alarm log indicates which power module generated the alarm: 1 = left most inverter module.
Index FC 300 Programming Guide Index Cabling CAN Protocol 10-00 Abbreviations Capacitance Output Filter 14-56 AC brake Max. Current 2-16 Catch Up Access To Main Menu W/o Password 0-61 Catch Up/slow Down Value 3-12 Access To Quick Menu W/o Password 0-66...
Page 200
Index FC 300 Programming Guide Dead Time Compensation 14-06 Flying Start 1-73 Default Settings 1, 159 Flystart Test Pulses Current 1-58 Defined Parameters 15-92 Flystart Test Pulses Frequency 1-59 Defined Parameters (1) 9-80 Forward Open Defined Parameters (2) 9-81 Freeze Output Defined Parameters (3) 9-82 [Freq.
Page 201
Index FC 300 Programming Guide Motor Angle 16-20 Motor Angle Offset 1-41 Motor Construction 1-10 Language 0-01 Motor Cont. Rated Torque 1-26 Language Package 1 Motor Control Principle 1-01 Language Package 2 Motor Cosphi 14-43 Language Package 3 Motor Current 1-24...
Page 202
Index FC 300 Programming Guide Profidrive OFF3 Select 8-58 Profile Number 9-65 Programming Set-up 9-70 Parameter Access Protection Mode Parameter Edit 9-27 Protocol 8-30 Parameter Info Protocol Selection 17-20 Parameter Metadata 15-99 Pulse Filter Time Constant #29 5-54 Parameter Selection...
Page 203
Index FC 300 Programming Guide Rated Motor Speed Speed PID Integral Time 7-03 Speed PID Lowpass Filter Time 7-06 Readout Bus Off Counter 10-07 Speed PID Proportional Gain 7-02 94, 156 Readout Filtering 8-08 [Speed RPM] 16-17 Readout Receive Error Counter 10-06...
Page 204
Index FC 300 Programming Guide Term. X48/2 High Current 35-43 Torque PI Proportional Gain 7-12 Term. X48/2 High Ref./feedb. Value 35-45 Torque Ramp Time 2-27 Term. X48/2 Low Current 35-42 Torque Ref 2-26 Term. X48/2 Low Ref./feedb. Value 35-44 Tracking Error 4-35 Term.