FC 300 Design Guide
Function:
Select the second Boolean (TRUE or FALSE)
input for the selected logic rule. See par.
13-40 for further explanation.
13-43 Logic Rule Operator 2
Array [4]
Option:
*
Disabled
And
Or
And not
Or not
Not and
Not or
Not and not
Not or not
Function:
Select the second logical operator to be used
on the boolean input calculated in par. 13-40,
13-41, and 13-42, and the boolean input
coming from par. 13-42.
[13-44] signifies the boolean input of par. 13-44.
[13-40/13-42] signifies the boolean input
calculated in par. 13-40, 13-41, and 13-42.
DISABLED [0] (factory setting) . select this
option to ignore par. 13-44.
AND [1] evaluates the expression [13-
40/13-42] AND [13-44].
OR [2] evaluates the expression [13-40/13-
42] OR [13-44].
AND NOT [3] evaluates the expression
[13-40/13-42] AND NOT [13-44].
OR NOT [4] evaluates the expression
[13-40/13-42] OR NOT [13-44].
NOT AND [5] evaluates the expression NOT
[13-40/13-42] AND [13-44].
NOT OR [6] evaluates the expression NOT
[13-40/13-42] OR [13-44].
NOT AND NOT [7] evaluates the expression NOT
[13-40/13-42] and evaluates AND NOT [13-44].
NOT OR NOT [8] evaluates the expression NOT
[13-40/13-42] OR NOT [13-44].
13-44 Logic Rule Boolean 3
Array [4]
default setting
( )
display text
*
232
How to Program
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
Select the third Boolean (TRUE or FALSE) input
for the selected logic rule.
13-5* States
"
Parameters for Programming the Smart
Logic Controller.
[ ]
value for use in communication via serial communication port
MG.33.B6.22 - VLT is a registered Danfoss trademark
Option:
*False
True
Running
In range
On reference
Torque limit
Current limit
Out of current range
Below I low
Above I high
Out of speed range
Below speed low
Above speed high
Out of feedb. range
Below feedb. low
Above feedb. high
Thermal warning
Line voltage out of range
Reversing
Warning
Alarm (trip)
Alarm (trip lock)
Comparator 0
Comparator 1
Comparator 2
Comparator 3
Logic rule 0
Logic rule 1
Logic rule 2
Logic rule 3
Timeout 0
Timeout 1
Timeout 2
Digital input DI18
Digital input DI19
Digital input DI27
Digital input DI29
Digital input DI32
Digital input DI33
Start command
Drive stopped
Function:
[0]
[1]
[2]
[3]
[4]
[5]
[6]
[7]
[8]
[9]
[10]
[11]
[12]
[13]
[14]
[15]
[16]
[17]
[18]
[19]
[20]
[21]
[22]
[23]
[24]
[25]
[26]
[27]
[28]
[29]
[30]
[31]
[32]
[33]
[34]
[35]
[36]
[37]
[38]
[39]
[40]

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents