FC 300 Design Guide
9-65 Profile Number
Option:
Read only
0 - 0
Function:
This parameter contains the profile identification.
Byte 1 contains the profile number and byte 2
the version number of the profile.
NOTE
This parameter is not visible via LCP.
9-70 Edit Set-up
Option:
Factory setup
*
Setup 1
Setup 2
Setup 3
Setup 4
Active setup
Function:
Select the set-up to be edited.
Select Set-up 1-4 [1]-[4] to edit a specific set-up.
Select Active set-up [9] to follow the active
set-up selected in par. 0-10.
Select Factory set-up [0] for default data. This
option can be used as a data source to return
the other set-ups to a known state.
This parameter is unique to LCP and fieldbuses.
See also par. 0-11 Edit set-up.
9-71 Save Data Values
Option:
*
Off
Store edit setup
Store all set-ups
Function:
Parameter values changed via Profibus are not
automatically stored in non-volatile memory. Use
this parameter to activate a function that stores
parameter values in the EEPROM non-volatile
memory, so changed parameter values will
be retained at power-down.
Select Off [0] to deactivate the non-volatile
storage function.
*
default setting
( )
display text
How to Program
Select Store edit setup [1] to store all parameter
values in the set-up selected in par. 9-70 in the
non-volatile memory. The selection returns to Off
[0] when all values have been stored.
*
0
Select Store all set-ups [2] to store all parameter
values for all set-ups in the non-volatile memory.
The selection returns to Off [0] when all parameter
values have been stored.
*
[0]
Select Power-on reset [1] to reset the frequency
[1]
converter upon power-up, as for power-cycle.
[2]
Select Comm. option reset [3] to reset the Profibus
[3]
option only, useful after changing certain settings
[4]
in parameter group 9-**, e.g. par. 9-18.
[9]
When reset, the frequency converter disappears
from the fieldbus, which may cause a
communication error from the master.
This parameter displays a list of all the
defined frequency converter parameters
[0]
available for Profibus.
[1]
[2]
[ ]
value for use in communication via serial communication port
MG.33.B6.22 - VLT is a registered Danfoss trademark
9-72 Drive Reset
Option:
No action
Power-on reset
Power-on reset prep
Comm. option reset
Function:
9-80 Defined Parameters (1)
Array [1000]
Option:
No LCP access
Read-only
0 - 9999
Function:
9-81 Defined Parameters (2)
Array [1000]
Option:
No LCP access
Read-only
0 - 9999
[0]
[1]
[2]
[3]
*
0
*
0
219