Danfoss FC 300 Design Manual page 299

Vlt automationdrive
Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide
Description of Alarm Word, Warning Word, and extended Status Word
Alarm Word Extended Status Word
Bit
Hex
0
00000001
1
00000002
2
00000004
3
00000008
4
00000010
5
00000020
6
00000040
7
00000080
8
00000100
9
00000200
10
00000400
11
00000800
12
00001000
13
00002000
14
00004000
15
00008000
16
00010000
17
00020000
18
00040000
19
00080000
20
00100000
21
00200000
22
00400000
23
00800000
24
01000000
25
02000000
26
04000000
27
08000000
28
10000000
29
20000000
31
80000000
The alarm words, warning words and extended status words can be read out via serial bus or
optional ser. com. bus for diagnosis. See also par. 16-90, 16-92, and 16-94.
WARNING 1
10 V low:
The 10 V voltage from terminal 50 on the
control card is below 10 V.
Remove some of the load from terminal 50,
as the 10 V supply is overloaded. Max. 15
mA or minimum 590 Ω.
WARNING/ALARM 2
Live zero error:
The signal on terminal 53 or 54 is less than
50% of the value set in par. 6-10, 6-12,
6-20, or 6-22 respectively.
Troubleshooting
Dec
AlarmWord
1
Brake Check
2
Pwr. Card Temp
4
Ground Fault
8
Ctrl.Card Temp
16
Ctrl. Word TO
32
Overcurrent
64
Torque Limit
128
Thrmstr overld
256
Motor ETR Over
512
Inverter Overld.
1024
DC undervolt
2048
DC overvolt
4096
Short Circuit
8192
Soft-charge Fault
16384
Line ph. Loss
32768
AMA Not OK
65536
Live Zero Error
131072
Internal Fault
262144
Brake Overload
524288
U phase Loss
1048576
V phase Loss
2097152
W phase Loss
4194304
Ser. com. bus
fault
8388608
24 V Supply Low
16777216
Line Failure
33554432
1.8 V Supply Low
67108864
Brake Resistor
134217728
Brake IGBT
268435456
Option Change
536870912
Drive Initialized
2147483648
Mech. brake low
MG.33.B6.22 - VLT is a registered Danfoss trademark
WarningWord
Brake Check
Pwr. Card Temp
Ground Fault
Ctrl.Card Temp
Ctrl. Word TO
Overcurrent
Torque Limit
Thrmstr overld
Motor ETR Over
Inverter Overld.
DC undervolt
DC overvolt
DC Voltage Low
DC Voltage High
Line ph. Loss
No Motor
Live Zero Error
10 V Low
Brake Overload
Brake Resistor
Brake IGBT
Speed Limit
Ser. com. bus fault
24 V Supply Low
Line Failure
Current Limit
Low Temp
Voltage Limit
Unused
Unused
Extended Status Word
WARNING/ALARM 3
No motor:
No motor has been connected to the output of
the adjustable frequency drive.
WARNING/ALARM 4
Mains phase loss:
A phase is missing on the supply side, or the
line voltage imbalance is too high.
This message also appears in case of a fault in the
input rectifier on the adjustable frequency drive.
Check the supply voltage and supply currents
to the adjustable frequency drive.
ExtendedStatusWord
Ramping
AMA Running
Start CW/CCW
Slow-down
Catch up
Feedback High
Feedback Low
Output Current High
Output Current Low
Output Freq High
Output Freq Low
Brake Check OK
Braking Max
Braking
Out of Speed Range
OVC Active
299