Function:
Parameters for configuring the scaling and
output functions of pulse outputs. The pulse
outputs are designated to terminals 27 or 29.
Select terminal 27 output in par. 5-01 and
terminal 29 output in par. 5-02.
5-60 Terminal 27 Pulse Output Variable
Option:
*
No operation
Function:
Select the variable for viewing on the
terminal 27 display.
This parameter cannot be adjusted while
the motor is running.
5-62 Pulse Output Maximum Frequency #27
Range:
0 - 32000 Hz
Function:
Set the maximum frequency for terminal
27, corresponding to the output variable
selected in par. 5-60.
This parameter cannot be adjusted while
the motor is running.
5-63 Terminal 29 Pulse Output Variable
Option:
*
No operation
Function:
Select the variable for viewing on the terminal
29 display. This parameter is available
for the FC 302 only.
This parameter cannot be adjusted while
the motor is running.
*
default setting
( )
display text
How to Program
[0]
[51]
[100]
[101]
[102]
[103]
Set the maximum frequency for terminal 29
[104]
corresponding to the output variable set in par. 5-63.
[105]
This parameter cannot be adjusted while
[106]
the motor is running.
[107]
[108]
*
Select the variable for read-out on terminal
X30/6. This parameter cannot be adjusted
while the motor is running.
This parameter is active when option module MCB
101 is installed in the adjustable frequency drive.
quency #X30/6
[0]
*
Select the maximum frequency on terminal
X30/6 referring to the output variable in par.
5-66. This parameter cannot be adjusted
while the motor is running.
This parameter is active when option module MCB
*
5000Hz
101 is mounted in the adjustable frequency drive.
5-7* 24 V Encoder Input
"
Parameters for configuring the 24 V encoder.
Connect the 24 V encoder to terminal 12 (24 V
DC supply), terminal 32 (Channel A), terminal 33
(Channel B), and terminal 20 (GND). The digital
inputs 32/33 are active for encoder inputs when 24
V encoder is selected in par. 1-02 and par. 7-00.
The encoder used is a dual channel (A and B) 24
V type. Max input frequency: 110 kHz.
[0]
[ ]
value for use in communication via serial communication port
MG.33.B6.22 - VLT is a registered Danfoss trademark
5-65 Pulse Output Maximum Frequency #29
Range:
0 - 32000 Hz
Function:
5-66 Terminal X30/6 Pulse Output Variable
Option:
No operation
Function:
5-68 Pulse Output Maximum Fre-
Option:
No operation
Function:
*
5000Hz
[0]
[0]
199