FC 300 Design Guide
How to Program
Bit 04, ON 2/OFF 2
Bit 04 = "0": Bit 01 of the Control word is "0". Bit 04 = "1": Bit 01 of the Control word is "1".
Bit 05, ON 3/OFF 3
Bit 05 = "0": Bit 02 of the Control word is "0". Bit 05 = "1": Bit 02 of the Control word is "1".
Bit 06, Start possible/Start not possible
Bit 06 is always "0" if you select FC Drive in par. 8-10. If you select PROFIdrive in par. 8-10,
bit 06 is "1" after a switch-off acknowledgement, after activation of OFF2 or OFF3, and after
switching on mains voltage. Start is not possible. The adjustable frequency drive is reset with
bit 00 of the Control word set to "0" and bit 01, 02, and 10 set to "1".
Bit 07, No warning/Warning
Bit 07 = "0": No unusual situation. Bit 07 = "1": There is an unusual status in the adjustable frequency
drive. For more information about warnings - see the FC 300 Profibus Operating Instructions.
Bit 08, Speed ≠ reference / Speed = reference:
Bit 08 = "0": The motor speed deviates from the set speed reference value. This occurs
e.g. when the speed is changed during start/stop through ramp-up/down. Bit 08 = "1": The
motor speed corresponds to the set speed reference value.
Bit 09, Local operation/Bus control
Bit 09 = "0": Indicates that the adjustable frequency drive is stopped via [Stop] or that Local is selected in
par. 0-02. Bit 09 = "1": The adjustable frequency drive is controlled through the serial interface.
Bit 10, Out of frequency limit/Frequency limit OK
Bit 10 = "0": The output frequency is outside the limits set in par. 4-11 and par. 4-13 (Warnings: Motor
speed low or high limit). Bit 10 = "1": The output frequency is within the indicated limits.
Bit 11, No operation/Operation
Bit 11 = "0": The motor is not running. Bit 11 = "1": A start signal is active or
the output frequency is higher than 0 Hz.
Bit 12, Drive OK/Stopped, autostart
Bit 12 = "0": No temporary overloading of the inverter. Bit 12 = "1": The inverter stops due to overload. How-
ever, the adjustable frequency drive is not switched off (tripped) and will restart after the overloading stops.
Bit 13, Voltage OK/Voltage exceeded
Bit 13 = "0": The adjustable frequency drive voltage limits are not exceeded. Bit 13 = "1": The
direct voltage in the drive intermediate circuit is too low or too high.
Bit 14, Torque OK/Torque exceeded
Bit 14 = "0": The motor current is below the moment limit selected in par. 4-18. Bit 14
= "1": The torque limit selected in par. 4-18 is exceeded.
Bit 15, Timer OK/Timer exceeded
Bit 15 = "0": The timers for the thermal motor protection and adjustable frequency drive thermal protection
have not exceeded 100%. Bit 15 = "1": One of the timers has exceeded 100%.
default setting
( )