Minimum cross-section to control wires ............................................................. 0.0004 in.
Digital inputs:
Programmable digital inputs ................................................................... FC 301: 4 (5) / FC 302: 4 (6)
Terminal number ....................................................................................... 18, 19, 27
Logic ............................................................................................................................ PNP or NPN
Voltage level .................................................................................................................. 0 - 24 V DC
Voltage level, logic'0' PNP ................................................................................................... < 5 V DC
Voltage level, logic'1' PNP ................................................................................................. > 10 V DC
Voltage level, logic '0' NPN
Voltage level, logic '1' NPN
Maximum voltage on input ................................................................................................... 28 V DC
Input resistance, R
...................................................................................................... approx. 4 kΩ
i
Safe stop Terminal 37
Terminal 37 is fixed PNP logic
Voltage level .................................................................................................................. 0 - 24 V DC
Voltage level, logic'0' PNP .................................................................................................... < 4 V DC
Voltage level, logic'1' PNP ................................................................................................... >20 V DC
Nominal input current at 24 V ........................................................................................... 50 mA rms
Nominal input current at 20 V ........................................................................................... 60 mA rms
Input capacitance .................................................................................................................. 400 nF
All digital inputs are galvanically isolated from the supply voltage (PELV) and other high-voltage terminals.
1) Terminals 27 and 29 can also be programmed as output.
2) Except safe stop input Terminal 37.
3) Terminal 37 is only available in the FC 302. It can only be used as safe stop input. Terminal 37 is suitable
for category 3 installations according to EN 954-1 (safe stop according to category 0 EN 60204-1) as
required by the EU Machinery Directive 98/37/EC. Terminal 37 and the Safe Stop function are designed in
conformance with EN 60204-1, EN 50178, EN 61800-2, EN 61800-3, and EN 954-1. For correct and safe
use of the Safe Stop function, follow the related information and instructions in the Design Guide.
4) FC 302 only.
FC 300 Selection
2)
............................................................................................ > 19 V DC
2)
............................................................................................. < 14 V DC
4)
:
MG.33.B6.22 - VLT is a registered Danfoss trademark
2
(0.25 mm
2
)
1)
, 29
4)
, 32, 33,
61

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents