Parameters: Digital In/Out - Danfoss FC 300 Design Manual

Vlt automationdrive
Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

FC 300 Design Guide

Parameters: Digital In/Out

"
5-** Digital In/Out
"
Parameter group for configuring the digital
input and output.
5-0* Digital I/O Mode
"
Parameters for configuring the IO mode. NPN/PNP
and setting up IO to input or output.
5-00 Digital I/O Mode
Option:
*
PNP
NPN
Function:
Digital inputs and programmed digital outputs
are pre-programmable for operation either
in PNP or NPN systems.
Select PNP [0] systems for action on positive
directional pulses (). PNP systems are
pulled down to GND.
Select NPN [1] systems for action on negative
directional pulses (). NPN systems are pulled up to
+ 24 V, internally in the frequency converter.
This parameter cannot be adjusted while
the motor is running.
5-01 Terminal 27 Mode
Option:
*
Input
Output
Function:
Select Input [0] to define terminal 27
as a digital input.
Select Output [1] to define terminal 27
as a digital output.
This parameter cannot be adjusted while
the motor is running.
5-02 Terminal 29 Mode
Option:
*
Input
Output
Function:
Select Input [0] to define terminal 29
as a digital input.
Select Output [1] to define terminal 29
as a digital output.
default setting
( )
display text
*
192
How to Program
This parameter is available for the FC 302 only.
This parameter cannot be adjusted while
the motor is running.
5-1* Digital Inputs
"
Parameters for configuring the input functions
for the input terminals.
The digital inputs are used for selecting various
functions in the frequency converter. All digital
inputs can be set to the following functions:
[0]
[1]
[0]
[1]
[0]
[1]
[ ]
value for use in communication via serial communication port
MG.33.B6.22 - VLT is a registered Danfoss trademark
Digital input function
Select
No operation
[0]
Reset
[1]
Coast inverse
[2]
Coast and reset inverse
[3]
Quick stop inverse
[4]
DC-brake inverse
[5]
Stop inverse
[6]
Start
[8]
Latched start
[9]
Reversing
[10]
Start reversing
[11]
Enable start forward
[12]
Enable start reverse
[13]
Jog
[14]
Preset reference on
[15]
Preset ref bit 0
[16]
Preset ref bit 1
[17]
Preset ref bit 2
[18]
Freeze reference
[19]
Freeze output
[20]
Speed up
[21]
Speed down
[22]
Set-up select bit 0
[23]
Set-up select bit 1
[24]
Precise stop inverse
[26]
Precises start, stop
[27]
Catch up
[28]
Slow down
[29]
Counter input
[30]
Pulse input
[32]
Ramp bit 0
[34]
Ramp bit 1
[35]
Mains failure inverse
[36]
Latched precise start
[40]
Latched precise stop
[41]
inverse
DigiPot Increase
[55]
DigiPot Decrease
[56]
DigiPot Clear
[57]
Counter A (up)
[60]
Counter A (down)
[61]
Reset Counter A
[62]
Counter B (up)
[63]
Counter B (down)
[64]
Reset Counter B
[65]
Terminal
All *term 32, 33
All
All *term 27
All
All
All
All
All *term 8
All
All *term 19
All
All
All
All *term 29
All
All
All
All
All
All
All
All
All
All
18, 19
18, 19
All
All
29, 33
29, 33
All
All
All
18, 19
18, 19
All
All
All
29, 33
29, 33
All
29, 33
29, 33
All