FC 300 Design Guide
16-33 Braking Energy /2 min
Range:
0.000 - 670510 HP [0.000 - 500.000 kW]
Function:
View the braking energy transmitted to an external
brake resistor. The mean power is calculated on an
average basis for the most recent 120 seconds.
16-34 Heatsink Temp.
Range:
0-491°F [0-255°C]
Function:
View the adjustable frequency drive heatsink
temperature. The cut-out limit is 203 ± 9°F
[90 ± 5°C], and the motor cuts back in at
158 ± 9°F [60 ± 5°C].
16-35 Inverter Thermal
Range:
0 - 0 %
Function:
View the percentage load on the inverter.
16-36 Inv. Nom. Current
Range:
0.01 - 10000.00 A
Function:
View the inverter nominal current, which should
match the nameplate data on the connected
motor. The data are used for calculation of
torque, motor protection, etc.
16-37 Inv. Max. Current
Range:
0.01 - 10000.00 A
Function:
View the inverter maximum current, which should
match the nameplate data on the connected
motor. The data are used for calculation of
torque, motor protection, etc.
16-38 SL Controller State
Range:
0 - 0
*
default setting
( )
display text
How to Program
*
0.000 HP [0.000 kW]
*
32°F [0°C]
*
0 %
*
A
*
A
*
0
[ ]
value for use in communication via serial communication port
MG.33.B6.22 - VLT is a registered Danfoss trademark
Function:
View the state of the event under execution
by the SL controller.
16-39 Control Card Temp.
Range:
0-212°F [0-100°C]
Function:
View the temperature on the control card,
stated in °F [°C].
16-40 Logging Buffer Full
Option:
*
No
Yes
Function:
View whether the logging buffer is full (see par.
15-1*). The logging buffer will never be full when
par. 15-13 Logging Mode is set to Log always [0].
16-5* Ref. & Feedb.
"
Parameters for reporting the reference
and feedback input.
16-50 External Reference
Range:
0.0 - 0.0
Function:
View the total reference, the sum of digital,
analog, preset, bus and freeze references,
plus catch-up and slow-down.
16-51 Pulse Reference
Range:
0.0 - 0.0
Function:
View the reference value from programmed
digital input(s). The read-out can also reflect the
impulses from an incremental encoder.
16-52 Feedback [Unit]
Range:
0.0 - 0.0
Function:
View the feedback unit resulting from the selection
of unit and scaling in par. 3-00, 3-01, 3-02 and 3-03.
*
32°F [0°C]
[0]
[1]
*
0.0
*
0.0
*
0.0
247