FC 300 Design Guide
Parameters: DeviceNet
"
CAN Fieldbus
10-** DeviceNet CAN Ser. Com. Bus
"
Parameter group for DeviceNet CAN serial
communication bus parameters.
10-0* Common Settings
"
Parameter group for configuring common
settings for CAN fieldbus options.
10-00 CAN Protocol
Option:
CANopen
*
DeviceNet
Function:
View the active CAN protocol.
NOTE
The options depend on installed option.
10-01 Baud Rate Select
Option:
10 Kbps
20 Kbps
50 Kbps
100
*
125 Kbps
250 Kbps
500 Kbps
Function:
Select the fieldbus transmission speed. The
selection must correspond to the transmission speed
of the master and the other fieldbus nodes.
10-02 MAC ID
Option:
0 - 127 N/A
Function:
Selection of station address. Every station
connected to the same DeviceNet network must
have an unambiguous address.
10-05 Readout Transmit Error Counter
Range:
0 - 255
*
default setting
( )
How to Program
[0]
[1]
[16]
[17]
[18]
[19]
[20]
[21]
[22]
*
63 N/A
display text
[ ]
value for use in communication via serial communication port
MG.33.B6.22 - VLT is a registered Danfoss trademark
Function:
View the number of CAN control transmission
errors since the last power-up.
10-06 Readout Receive Error Counter
Range:
0 - 255
Function:
View the number of CAN control receipt errors
since the last power-up.
10-07 Readout Bus Off Counter
Range:
0 - 1000
Function:
View the number of Bus Off events since
the last power-up.
10-1* DeviceNet
"
Parameters specific to the DeviceNet fieldbus.
10-10 Process Data Type Selection
Option:
Instance 100/150
Instance 101/151
Instance 20/70
Instance 21/71
Function:
Select the instance (telegram) for data transmission.
The instances available are dependent upon the
setting of par. 8-10 Control Word Profile.
When par. 8-10 is set to [0] FC profile, par. 10-10
options [0] and [1] are available.
When par. 8-10 is set to [5] ODVA, par. 10-10
options [2] and [3] are available.
Instances 100/150 and 101/151 are
Danfoss-specific. Instances 20/70 and
21/71 are ODVA-specific AC drive profiles.
For guidelines in telegram selection, please refer
to the DeviceNet Instruction Manual.
Note that a change to this parameter will
be executed immediately.
10-11 Process Data Config Write
Option:
*
0 None
*
16-80 Fieldbus CTW 1 (Fixed)
0
*
0
*
0
[0]
[1]
[2]
[3]
221