6.6.3 Restoring Factory Default Settings Using the Recommended Initialization
Context:
LOSS OF DATA
Restoring default settings results in a loss of programming, motor data, localization, and monitoring records.
To create a back-up, upload data to the LCP before initialization. See
-
1. Press [Main Menu] twice to access parameters.
2. Go to parameter 14-22 Operation Mode and press [OK].
Parameter 14-22 Operation Mode does not reset the following settings:
•
Running hours.
•
Serial communication options.
•
Personal menu settings.
•
Fault log, alarm log, and other monitoring functions.
3. Scroll to Initialization and press [OK].
4. Remove power to the unit and wait for the display to turn off.
5. Apply power to the unit. Default parameter settings are restored during start-up. Start-up takes slightly longer than normal.
6. After alarm 80, Drive initialized appears, press [Reset].
6.6.4 Restoring Factory Default Settings Using Manual Initialization
Context:
LOSS OF DATA
Restoring default settings results in a loss of programming, motor data, localization, and monitoring records.
To create a back-up, upload data to the LCP before initialization. See
-
Procedure
1. Remove power to the unit and wait for the display to turn off.
2. Press and hold [Status], [Main Menu], and [OK] simultaneously while applying power to the unit (approximately 5 s or until an
audible click sounds and the fan starts).
Manually initializing does not reset the following parameter settings:
•
Parameter 15-00 Operating Hours
•
Parameter 15-03 Power Up's
•
Parameter 15-04 Over Temp's
•
Parameter 15-05 Over Volt's
Start-up takes slightly longer than normal.