FC 300 Design Guide
Function:
Set the motor current for release of the mechanical
brake, when a start condition is present. The upper
limit is specified in par. 16-37 Inv. Max. Current.
2-21 Activate Brake Speed [RPM]
Range:
0 - par. 4-53 RPM
Function:
Set the motor speed for activation of the
mechanical brake, when a stop condition is
present. The upper speed limit is specified in
par. 4-53 Warning Speed High.
2-22 Activate Brake Speed [Hz]
Range:
0 - Max. speed
Function:
Set the motor frequency for activation of the
mechanical brake, when a stop condition is present.
2-23 Activate Brake Delay
Range:
0.0 - 5.0 s
Function:
Enter the brake delay time of the coast after
ramp-down time. The shaft is held at zero
speed with full holding torque. Ensure that the
mechanical brake has locked the load before
the motor enters coast mode. See Control
of Mechanical Brake section.
default setting
( )
display text
*
176
How to Program
*
0RPM
*
0 Hz
*
0.0s
[ ]
value for use in communication via serial communication port