FC 300 Design Guide
Line Supply 3 x 380 - 500 VAC (FC 302)
"
3 x 380 - 480 VAC (FC 301)
FC 301/FC 302
Typical Shaft Output [kW]
Output current
Continuous
(3 x 380-440 V) [A]
Intermittent
(3 x 380-440 V) [A]
Continuous
(3 x 440-500 V) [A]
Intermittent
(3 x 440-500 V) [A]
Continuous KVA
(400 V AC) [KVA]
Continuous KVA
(460 V AC) [KVA]
Max. cable size
(line, motor, brake)
[AWG]
Max. input current
Continuous
(3 x 380-440 V) [A]
Intermittent
(3 x 380-440 V) [A]
Continuous
(3 x 440-500 V) [A]
Intermittent
(3 x 440-500 V) [A]
Max. pre-fuses
Environment
Estimated power loss
at rated max. load [W]
Enclosure IP 20
Weight,
enclosure IP 20 [kg]
Efficiency
56
FC 300 Selection
0,25 0.37
-
1.3
-
2.1
-
1.2
-
1.9
-
0.9
-
0.9
-
2)
[mm
2
]
-
1.2
-
1.9
-
1.0
-
1.6
1)
[A]
-
10
-
35
4)
-
4.7
4)
-
0.93
MG.33.B6.22 - VLT is a registered Danfoss trademark
0.55
0.75 1.1
1.5
2.2
1.8
2.4
3
4.1
5.6
2.9
3.8
4.8
6.6
9.0
1.6
2.1
2.7
3.4
4.8
2.6
3.4
4.3
5.4
7.7
1.3
1.7
2.1
2.8
3.9
1.3
1.7
2.4
2.7
3.8
24 - 10 AWG
0.0079-0.1575 in [0.2-4 mm]
1.6
2.2
2.7
3.7
5.0
2.6
3.5
4.3
5.9
8.0
1.4
1.9
2.7
3.1
4.3
2.2
3.0
4.3
5.0
6.9
10
10
10
10
20
42
46
58
62
88
4.7
4.8
4.8
4.9
4.9
0.95
0.96 0.96
0.97
0.97
3
3.7
4
5.5
7.5
7.2
-
10
13
11.5
-
16
20.8
25.6
6.3
-
8.2
11
14.5
10.1
-
13.1
17.6
23.2
5.0
-
6.9
9.0
11.0
5.0
-
6.5
8.8
11.6
24 - 10 AWG
-
0.0079-0.1575 in
2
[0.2-4 mm]
6.5
-
9.0
11.7
14.4
10.4
-
14.4
18.7
23.0
5.7
-
7.4
9.9
13.0
9.1
-
11.8
15.8
20.8
20
-
20
32
116
-
124
187
255
4.9
-
4.9
6.6
6.6
0.97
-
0.97
0.97
0.97
16
2
32