How to Program

2.1.8 Initial Commissioning

The easiest way of carrying out the initial commissioning is by using the quick menu button and follow the quick set-up
procedure using LCP 102 (read table from left to right). The example applies to open-loop applications.
Press
Quick
Menu
0-01 Language
1-20 Motor Power [kW]
1-22 Motor Voltage
1-23 Motor Frequency
1-24 Motor Current
1-25 Motor Nominal Speed
5-12 Terminal 27 Digital Input
1-29 Automatic Motor Adaptation
(AMA)
3-02 Minimum Reference
3-03 Maximum Reference
3-41 Ramp 1 Ramp up Time
3-42 Ramp 1 Ramp Down Time
3-13 Reference Site
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Q2 Quick Menu
OK
Set language
OK
Set motor nameplate power
OK
Set nameplate voltage
OK
Set nameplate frequency
OK
Set nameplate current
OK
Set Nameplate speed in RPM
If terminal default is Coast
inverse, it is possible to change
OK
this setting to No function. No
connection to terminal 27 is
then needed for running AMA
Set desired AMA function.
OK
Enabling complete AMA is
recommended
Set the minimum speed of the
OK
motor shaft
Set the maximum speed of the
OK
motor shaft
Set the ramping-up time with
OK
reference to synchronous
motor speed, ns.
Set the ramping-down time
OK
with reference to synchronous
motor speed, ns.
Set the site from where the
OK
reference must work
®
MG33MD22 - VLT
is a registered Danfoss trademark
OK
2
2
2-7