Parameter Descriptions

0-04 Operating State at Power-up (Hand)

Option:
Function:
Selects the operating mode upon
reconnection of the Adjustable frequency
drive to AC line voltage after power-down in
hand (local) operation mode.
[0]
Resume
Restarts the Adjustable frequency drive
maintaining the same local reference and the
same start/stop settings (applied by [HAND
ON/OFF]) as before the Adjustable frequency
drive was powered down.
[1]
Forced stop,
Restarts the Adjustable frequency drive with
*
ref=old
a saved local reference, after AC line voltage
reappears and after pressing [HAND ON].
[2]
Forced stop,
Resets the local reference to 0 upon
ref=0
restarting the Adjustable frequency drive.

3.2.2 0-1* Set-up Operations

Define and control the individual parameter set-ups.
The Adjustable frequency drive has four parameter set-ups
that can be programmed independently of each other. This
makes the Adjustable frequency drive very flexible and
able to solve advanced control functionality problems,
often saving the cost of external control equipment. For
example, these can be used to program the Adjustable
frequency drive to operate according to one control
scheme in one set-up (e.g., motor 1 for horizontal
movement) and another control scheme in another set-up
(e.g., motor 2 for vertical movement). Alternatively they
can be used by an OEM machine builder to identically
program all their factory fitted adjustable frequency drives
for different machine types within a range to have the
same parameters and then during production/commis-
sioning simply select a specific set-up depending on which
machine the Adjustable frequency drive is installed on.
The active set-up (i.e., the set-up in which the Adjustable
frequency drive is currently operating) can be selected in
0-10 Active Set-up and is displayed in the LCP. Using Multi
set-up, it is possible to switch between set-ups with the
Adjustable frequency drive running or stopped, via digital
input or serial communication commands. If it is necessary
to change set-ups while running, ensure 0-12 This Set-up
Linked to is programmed as required. Using 0-11 Edit Set-
up, it is possible to edit parameters within any of the set-
ups whilst continuing the Adjustable frequency drive
operation in its Active Set-up which can be a different set-
up to that being edited. Using 0-51 Set-up Copy, it is
possible to copy parameter settings between the set-ups
to enable quicker commissioning if similar parameter
settings are required in different set-ups.
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide

0-10 Active Set-up

Option:
[0]
[1]
[2]
[3]
[4]
[9]
Use 0-51 Set-up Copy to copy a set-up to one or all other
set-ups. Stop the Adjustable frequency drive before
switching between set-ups where parameters marked 'not
changeable during operation' have different values. To
avoid conflicting settings of the same parameter within
two different set-ups, link the set-ups together using
0-12 This Set-up Linked to. Parameters which are 'not
changeable during operation' are marked FALSE in the
parameter lists in the section Parameter Lists.

0-11 Edit Set-up

Option:
[0]
[1]
[2]
[3]
[4]
[9]
®
MG33MD22 - VLT
is a registered Danfoss trademark
Function:
Select the set-up to control the Adjustable
frequency drive functions.
Factory
Cannot be changed. It contains the Danfoss
setup
data set, and can be used as a data source
when returning the other set-ups to a
known state.
Set-up 1
Set-up 1 [1] to Set-up 4 [4] are the four
*
separate parameter set-ups within which all
parameters can be programmed.
Set-up 2
Set-up 3
Set-up 4
Multi Set-up
Remote selection of set-ups using digital
inputs and the serial communication port.
This set-up uses the settings from 0-12 This
Set-up Linked to. Stop the Adjustable
frequency drive before making changes to
open-loop and closed-loop functions
Function:
Select the set-up to be edited (i.e.,
programmed) during operation: either the
active set-up or one of the inactive set-ups.
Factory setup Cannot be edited, but it is useful as a data
source for returning the other set-ups to a
known state.
Set-up 1
Set-up 1 [1] to Set-up 4 [4] can be edited
*
freely during operation, independently of
the active set-up.
Set-up 2
Set-up 3
Set-up 4
Active Set-up Can also be edited during operation. Edit
the chosen set-up from a range of sources:
LCP, FC RS-485, FC USB or up to five serial
communication bus sites.
3
3
3-3