Parameter Descriptions

3.21 Parameters: 35-** Sensor Input Option

3.21.1 35-0* Temp. Input Mode (MCB 114)

3
3
35-00 Term. X48/4 Temp. Unit
Select the unit to be used with temperature input X48/4 settings
and readouts:
Option:
[60]
*
[160]
35-01 Term. X48/4 Input Type
View the temperature sensor type detected at input X48/4:
Option:
[0]
*
[1]
[3]
[5]
[7]
35-02 Term. X48/7 Temp. Unit
Select the unit to be used with temperature input X48/7 settings
and readouts:
Option:
[60]
*
[160]
35-03 Term. X48/7 Input Type
View the temperature sensor type detected at input X48/7:
Option:
[0]
*
[1]
[3]
[5]
[7]
35-04 Term. X48/10 Temp. Unit
Select the unit to be used with temperature input X48/10
settings and readouts:
Option:
[60]
*
[160]
35-05 Term. X48/10 Input Type
View the temperature sensor type detected at input X48/10:
Option:
[0]
*
[1]
[3]
[5]
[7]
3-154
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Function:
°C
°F
Function:
Not Connected
PT100 2-wire
PT1000 2-wire
PT100 3-wire
PT1000 3-wire
Function:
°C
°F
Function:
Not Connected
PT100 2-wire
PT1000 2-wire
PT100 3-wire
PT1000 3-wire
Function:
°C
°F
Function:
Not Connected
PT100 2-wire
PT1000 2-wire
PT100 3-wire
PT1000 3-wire
MG33MD22 - VLT
35-06 Temperature Sensor Alarm Function
Select the alarm function:
Option:
[0]
Off
[2]
Stop
[5]
Stop and trip
*

3.21.2 35-1* Temp. Input X48/4 (MCB 114)

35-14 Term. X48/4 Filter Time Constant
Range:
0.001 s
[0.001 -
*
10.000 s]
35-15 Term. X48/4 Temp. Monitor
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/4. The temperature limits
can be set in 35-16 Term. X48/4 Low Temp. Limit and 35-17 Term.
X48/4 High Temp. Limit.
Option:
[0]
Disabled
*
[1]
Enabled
35-16 Term. X48/4 Low Temp. Limit
Range:
Application dependent
35-17 Term. X48/4 High Temp. Limit
Range:
Application dependent
3.21.3 35-2* Temp. Input X48/7 (MCB 114)
35-24 Term. X48/7 Filter Time Constant
Range:
0.001 s
[0.001 -
*
10.000 s]
®
is a registered Danfoss trademark
Function:
Function:
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/4. A high time constant
value improves dampening but also
increases the time delay through the
filter.
Function:
[Application dependant]
*
[Application dependant]
*
Function:
Enter the filter time constant. This is a
first-order digital low pass filter time
constant for suppressing electrical noise
in terminal X48/7. A high time constant
value improves dampening but also
increases the time delay through the
filter.
Function:
Function: