Load Depend. Setting; Low Speed Load Compensation; Slip Compensation; Resonance Dampening Time Constant - Danfoss VLT AutomationDrive Programming Manual

Hide thumbs Also See for VLT AutomationDrive:
Table of Contents

Advertisement

Parameter Descriptions
1-58 Flystart Test Pulses Current
Range:
3
3
1-59 Flystart Test Pulses Frequency
Range:
200 %
[0 - 500
*
%]

3.3.6 1-6* Load Depend. Setting

1-60 Low Speed Load Compensation

Range:
100 %
*
Motor size
0.34–10 hp [0.25–7.5 kW]
1-61 High Speed Load Compensation
Range:
100 %
*
Motor size
0.34–10 hp [0.25–7.5 kW]

1-62 Slip Compensation

Range:
Application
dependent
*
3-20
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
Function:
active when 1-73 Flying Start is enabled. This
parameter is only available in VVC
Function:
Control the percentage of the frequency for
the pulses used to detect the motor
direction. Increasing this value will reduce
the generated torque. 100% means 2 times
the slip frequency. The parameter is active
when 1-73 Flying Start is enabled. This
parameter is only available in VVC
Function:
[0 - 300 %]
Change-over
< 10Hz
Function:
[0 - 300 %]
Change-over
> 10Hz
Function:
[-500 -
Enter the % value for slip compensation
500 %]
to compensate for tolerances in the
MG33MD22 - VLT
FC 300 Programming Guide
1-62 Slip Compensation
Range:
plus
.
1-63 Slip Compensation Time Constant
Range:
plus
.
Size related
NOTE!
1-63 Slip Compensation Time Constant will not have effect
when 1-10 Motor Construction = [1] PM, non-salient SPM.
1-64 Resonance Dampening
Range:
100 %
*
NOTE!
1-64 Resonance Dampening will not have effect when
1-10 Motor Construction = [1] PM, non-salient SPM.

1-65 Resonance Dampening Time Constant

Range:
5 ms
*
NOTE!
1-65 Resonance Dampening Time Constant will not have
effect when 1-10 Motor Construction = [1] PM, non-salient
SPM.
1-66 Min. Current at Low Speed
Range:
100 %
*
®
is a registered Danfoss trademark
Function:
value of n
. Slip compensation is
M,N
calculated automatically, i.e., on the
basis of the rated motor speed n
This function is not active when
1-00 Configuration Mode is set to Speed
closed-loop [1] or Torque [2] Torque
control with speed feedback or when
1-01 Motor Control Principle is set to U/f
[0] special motor mode.
Function:
[0.05 - 5.00
Enter the slip compensation reaction
*
s]
speed. A high value results in slow
reaction, and a low value results in
quick reaction. If low-frequency
resonance problems arise, use a
longer time setting.
[0 - 500 %]
Function:
[5 - 50 ms] Set 1-64 Resonance Dampening and
1-65 Resonance Dampening Time Constant to
help eliminate high-frequency resonance
problems. Enter the time constant that
provides the best dampening.
[Application dependant]
.
M,N
Function:
Function:

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents