Parameter Descriptions
14-56 Capacitance Output Filter
Compensation function of the LC filter requires the per phase
equivalent star connected capacitance of the filter (3 times the
capacity between two phases when capacitance is 'Delta'
3
3
connection).
Range:
Application
dependent
*

14-57 Inductance Output Filter

Range:
Application
dependent
*
Application
dependent
*

3.15.6 14-7* Compatibility

The parameters in this group are for setting of compati-
bility for VLT 3000, VLT 5000 to FC 300.
14-72 VLT Alarm Word
Option:
[0] 0–4294967295 Read out the alarm word corresponding to
14-73 VLT Warning Word
Option:
[0] 0–4294967295 Read out the warning word corresponding to
3-134
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Function:
NOTE!
This is required for
correct compensation
in flux mode
(1-01 Motor Control
Principle)
[0.1 - 6500.0
uF]
Function:
[0.001 -
65.000 mH]
[0.001 -
Set the inductance of the
65.000 mH]
output filter. The value can be
found on the filter label.
NOTE!
This is required for correct
compensation in flux mode
(1-01 Motor Control
Principle)
Function:
VLT 5000.
Function:
VLT 5000.
MG33MD22 - VLT
14-74 Leg. Ext. Status Word
Range:
0
[0 - 4294967295 ] Read out the ext. status word
*

3.15.7 14-8* Options

14-80 Option Supplied by External 24VDC
Option:
Function:
[0]
No
Select No [0] to use the adjustable frequency drive's
24V DC supply.
[1]
Yes Select Yes [1] if an external 24V DC supply will be
*
used to power the option. Inputs/outputs will be
galvanically isolated from the drive when operated
from an external supply.
NOTE!
This parameter is only changing function by performing a
power cycle.

14-89 Option Detection

Selects the behavior of the Adjustable frequency drive when a
change in the option configuration is detected.
Option:
[0]
Protect Option
*
Config.
[1]
Enable Option
Change
14-90 Fault Level
Option:
Function:
[0]
Off
Use this parameter to customize fault levels. Use
*
[0] "Off" with caution as it will ignore all
warnings and alarms for the chosen source.
[1]
Warning
[2]
Trip
[3]
Trip Lock
®
is a registered Danfoss trademark
Function:
corresponding to VLT 5000
Function:
Freezes the current settings and
prevents unwanted changes when
missing or defective options are
detected.
Changes drive settings and is used
when modifying the system configu-
ration. This parameter setting will
return to [0] after an option change.