Parameter Descriptions

3-14 Preset Relative Reference

Range:
0.00 %
*
3
3
-100

3-15 Reference Resource 1

Option:
[0]
No function
[1]
Analog input 53
*
[2]
Analog input 54
[7]
Frequency input 29
[8]
Frequency input 33
[11] Local bus reference
[20] Digital pot.meter
[21] Analog input X30-11 (General Purpose I/O Option Module)
[22] Analog input X30-12 (General Purpose I/O Option Module)
[29] Analog Input X48/2
3-16 Reference Resource 2
Option:
3-36
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
[-100.00 - 100.00 %]
Y
Resulting
Relative
Z
actual
X
Z=X+X*Y/100
reference
Z
X
0
P 3-14
Function:
Select the reference input to be used
for the first reference signal.
3-15 Reference Resource 1,
3-16 Reference Resource 2 and
3-17 Reference Resource 3 define up to
three different reference signals. The
sum of these reference signals
defines the actual reference.
Function:
Select the reference input to be
used for the second reference
signal. 3-15 Reference Resource 1,
3-16 Reference Resource 2 and
3-17 Reference Resource 3 define up
to three different reference signals.
The sum of these reference signals
defines the actual reference.
MG33MD22 - VLT
3-16 Reference Resource 2
Function:
Option:
[0]
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Frequency input 29
[8]
Frequency input 33
[11]
Local bus reference
[20]
Digital pot.meter
*
[21]
Analog input X30-11
[22]
Analog input X30-12
[29]
Analog Input X48/2
3-17 Reference Resource 3
Option:
Y
100
%
[0]
No function
[1]
Analog input 53
[2]
Analog input 54
[7]
Frequency input 29
[8]
Frequency input 33
[11]
Local bus reference
*
[20]
Digital pot.meter
[21]
Analog input X30-11
[22]
Analog input X30-12
[29]
Analog Input X48/2

3-18 Relative Scaling Reference Resource

Option:
[0]
No function
*
®
is a registered Danfoss trademark
Function:
Function:
Select the reference input to be
used for the third reference signal.
3-15 Reference Resource 1,
3-16 Reference Resource 2 and
3-17 Reference Resource 3 define up
to three different reference signals.
The sum of these reference signals
defines the actual reference.
Function:
Select a variable value to be added to the
fixed value (defined in 3-14 Preset Relative
Reference). The sum of the fixed and
variable values (labeled Y in the figure
below) is multiplied by the actual reference
(labeled X in the figure below). The result
is then added to the actual reference (X
+X*Y/100) to give the resulting actual
reference.
Y
Resulting
Z
Relative
actual
X
Z=X+X*Y/100