Parameter Descriptions

1-53 Model Shift Frequency

Range:

1-54 Voltage reduction in fieldweakening

Range:
Function:
0 V
[0 - 100
The value of this parameter will reduce the
*
V]
maximal voltage available for the flux of the
Remote Site Products - 1-888-532-2706 - www.remotesiteproducts.com
http://www.remotesiteproducts.com/p-20872-Danfoss-131H4490-VLT-Automation-VT-Drive-VFD-FC302-460V-25-HP.aspx
FC 300 Programming Guide
Function:
With this parameter it is possible to
make an adjustment of the shifting
point where FC 302 changes
between Flux model 1 and Flux
model 2, which is useful in some
sensitive speed and torque control
applications.
f
x 0.1
f
x 0.125
N,M
N,M
Flux model 1
Flux model 2
f
P 1-53
out
Figure 3.2 1-00 Configuration
Mode = [1] Speed closed-loop or
[2] Torque and 1-01 Motor Control
Principle = [3] Flux w/motor
feedback
Variable Current - Flux model -
Sensorless
This model is used when
1-00 Configuration Mode is set to
Speed open-loop [0] and 1-01 Motor
Control Principle is set to Flux
sensorless [2].
In speed open-loop in flux mode,
the speed is determined by the
current measurement.
Below f
x 0.1, the Adjustable
norm
frequency drive runs on a variable
current model. Above f
x 0.125
norm
the Adjustable frequency drive runs
on a flux model.
f
f
x 0.1
x 0.125
N,M
N,M
Variable
current
Flux model 2
model
f
P 1-53
out
Figure 3.3 1-00 Configuration
Mode = [0] Speed open-loop,
1-01 Motor Control Principle = [2]
Flux sensorless
®
MG33MD22 - VLT
is a registered Danfoss trademark
1-54 Voltage reduction in fieldweakening
Range:
Function:
motor in fieldweakening, giving more voltage
available for torque. Be aware that a value that
is too high may cause stalling problems at high
speed.
1-55 U/f Characteristic - U
Range:
Function:
Application
[0.0 -
Enter the voltage at each
dependent
1000.0 V]
frequency point to manually form a
*
U/f characteristic matching the
motor.
The frequency points are defined
in 1-56 U/f Characteristic - F.
This parameter is an array
parameter [0-5] and is only
accessible when 1-01 Motor Control
Principle is set to U/f [0].
1-56 U/f Characteristic - F
Range:
Application
[Application
dependent
dependant]
*

1-58 Flystart Test Pulses Current

Range:
Function:
30 %
[0 - 200
Control the percentage of the magnetizing
*
%]
current for the pulses used to detect the
motor direction. Reducing this value will
reduce the generated torque. 100% means
nominal motor current. The parameter is
Function:
Enter the frequency points to
manually form a U/f-charac-
teristic matching the motor.
The voltage at each point is
defined in 1-55 U/f Characteristic
- U.
This parameter is an array
parameter [0-5] and is only
accessible when 1-01 Motor
Control Principle is set to U/f [0].
3-19
3
3